⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

32 Amp Cable Size at 15 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 5.65V (2.46%)
Voltage at Load224.9 VLine Loss: 164.4 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A13.7 V (5.95%)216.3 V22.59 V (9.82%)438.3 WDrop High
2.5 mm²24 A18 A8.22 V (3.57%)221.8 V13.56 V (5.89%)263.0 WDrop High
4 mm²32 A25 A5.14 V (2.23%)224.9 V8.47 V (3.68%)164.4 W✓ OK (≤3%)
6 mm²41 A32 A3.42 V (1.49%)226.6 V5.65 V (2.46%)109.6 W✓ OK (≤3%)
10 mm²57 A44 A2.05 V (0.89%)227.9 V3.39 V (1.47%)65.7 W✓ OK (≤3%)
16 mm²76 A59 A1.28 V (0.56%)228.7 V2.12 V (0.92%)41.1 W✓ OK (≤3%)
25 mm²101 A78 A0.82 V (0.36%)229.2 V1.36 V (0.59%)26.3 W✓ OK (≤3%)
35 mm²125 A97 A0.59 V (0.26%)229.4 V0.97 V (0.42%)18.8 W✓ OK (≤3%)
50 mm²151 A118 A0.41 V (0.18%)229.6 V0.68 V (0.29%)13.1 W✓ OK (≤3%)
70 mm²192 A150 A0.29 V (0.13%)229.7 V0.48 V (0.21%)9.4 W✓ OK (≤3%)
95 mm²232 A181 A0.22 V (0.09%)229.8 V0.36 V (0.16%)6.9 W✓ OK (≤3%)
120 mm²269 A210 A0.17 V (0.07%)229.8 V0.28 V (0.12%)5.5 W✓ OK (≤3%)
150 mm²309 A241 A0.14 V (0.06%)229.9 V0.23 V (0.1%)4.4 W✓ OK (≤3%)
185 mm²353 A275 A0.11 V (0.05%)229.9 V0.18 V (0.08%)3.6 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.04%)229.9 V0.14 V (0.06%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.03%)229.9 V0.11 V (0.05%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.02%)229.9 V0.08 V (0.04%)1.6 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 15 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 32A at 15 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 32A over 15m at 230V (voltage drop: 5.14V or 2.23%).

What is the power capacity of 32A at 230V?

At unity power factor, 32A at 230V supports 7.36 kW with a standard 32A circuit breaker.