500 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.93V (0.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.53V (0.38%)
Voltage at Load399.1 VLine Loss: 802.5 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A247.11 V (61.78%)152.9 V407.61 V (101.9%)214000.0 WDrop High
2.5 mm²24 A18 A148.26 V (37.07%)251.7 V244.57 V (61.14%)128400.0 WDrop High
4 mm²32 A25 A92.66 V (23.17%)307.3 V152.85 V (38.21%)80250.0 WDrop High
6 mm²41 A32 A61.78 V (15.44%)338.2 V101.9 V (25.48%)53500.0 WDrop High
10 mm²57 A44 A37.07 V (9.27%)362.9 V61.14 V (15.29%)32100.0 WDrop High
16 mm²76 A59 A23.17 V (5.79%)376.8 V38.21 V (9.55%)20062.5 WDrop High
25 mm²101 A78 A14.83 V (3.71%)385.2 V24.46 V (6.11%)12840.0 WDrop High
35 mm²125 A97 A10.59 V (2.65%)389.4 V17.47 V (4.37%)9171.4 WDrop High
50 mm²151 A118 A7.41 V (1.85%)392.6 V12.23 V (3.06%)6420.0 WDrop High
70 mm²192 A150 A5.3 V (1.32%)394.7 V8.73 V (2.18%)4585.7 WDrop High
95 mm²232 A181 A3.9 V (0.98%)396.1 V6.44 V (1.61%)3378.9 WDrop High
120 mm²269 A210 A3.09 V (0.77%)396.9 V5.1 V (1.27%)2675.0 WDrop High
150 mm²309 A241 A2.47 V (0.62%)397.5 V4.08 V (1.02%)2140.0 WDrop High
185 mm²353 A275 A2.0 V (0.5%)398.0 V3.3 V (0.83%)1735.1 WDrop High
240 mm²415 A324 A1.54 V (0.39%)398.5 V2.55 V (0.64%)1337.5 WDrop High
300 mm²477 A372 A1.24 V (0.31%)398.8 V2.04 V (0.51%)1070.0 WDrop High
400 mm²570 A445 A0.93 V (0.23%)399.1 V1.53 V (0.38%)802.5 W✓ OK (≤3%)

FAQ — 500 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 500A at 20 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 500A over 20m at 400V (voltage drop: 0.93V or 0.23%).

What is the power capacity of 500A at 400V?

At unity power factor, 500A at 400V supports 346.41 kW with a standard 500A circuit breaker.