⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

500 Amp Cable Size at 300 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.95V (1.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.93V (5.73%)
Voltage at Load393.1 VLine Loss: 6018.8 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3706.59 V (926.65%)0.0 V6114.14 V (1528.53%)3210000.0 WDrop High
2.5 mm²24 A18 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)1926000.0 WDrop High
4 mm²32 A25 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)1203750.0 WDrop High
6 mm²41 A32 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)802500.0 WDrop High
10 mm²57 A44 A555.99 V (139.0%)0.0 V917.12 V (229.28%)481500.0 WDrop High
16 mm²76 A59 A347.49 V (86.87%)52.5 V573.2 V (143.3%)300937.5 WDrop High
25 mm²101 A78 A222.4 V (55.6%)177.6 V366.85 V (91.71%)192600.0 WDrop High
35 mm²125 A97 A158.85 V (39.71%)241.1 V262.03 V (65.51%)137571.4 WDrop High
50 mm²151 A118 A111.2 V (27.8%)288.8 V183.42 V (45.86%)96300.0 WDrop High
70 mm²192 A150 A79.43 V (19.86%)320.6 V131.02 V (32.75%)68785.7 WDrop High
95 mm²232 A181 A58.53 V (14.63%)341.5 V96.54 V (24.13%)50684.2 WDrop High
120 mm²269 A210 A46.33 V (11.58%)353.7 V76.43 V (19.11%)40125.0 WDrop High
150 mm²309 A241 A37.07 V (9.27%)362.9 V61.14 V (15.29%)32100.0 WDrop High
185 mm²353 A275 A30.05 V (7.51%)369.9 V49.57 V (12.39%)26027.0 WDrop High
240 mm²415 A324 A23.17 V (5.79%)376.8 V38.21 V (9.55%)20062.5 WDrop High
300 mm²477 A372 A18.53 V (4.63%)381.5 V30.57 V (7.64%)16050.0 WDrop High
400 mm²570 A445 A13.9 V (3.47%)386.1 V22.93 V (5.73%)12037.5 W~ ≤5%

FAQ — 500 Amp Cable Size at 300 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 500A at 300 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 500A over 300m at 400V (voltage drop: 6.95V or 1.74%).

What is the power capacity of 500A at 400V?

At unity power factor, 500A at 400V supports 346.41 kW with a standard 500A circuit breaker.