500 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)19× 400 mm²Drop: 1.41V (2.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 44.12V (91.93%)
Voltage at Load46.6 VLine Loss: 703.9 W
Max Power & Breaker24.0 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7133.33 V (14861.11%)0.0 V11766.67 V (24513.89%)3566666.7 WDrop High
2.5 mm²24 A18 A4280.0 V (8916.67%)0.0 V7060.0 V (14708.33%)2140000.0 WDrop High
4 mm²32 A25 A2675.0 V (5572.92%)0.0 V4412.5 V (9192.71%)1337500.0 WDrop High
6 mm²41 A32 A1783.33 V (3715.28%)0.0 V2941.67 V (6128.47%)891666.7 WDrop High
10 mm²57 A44 A1070.0 V (2229.17%)0.0 V1765.0 V (3677.08%)535000.0 WDrop High
16 mm²76 A59 A668.75 V (1393.23%)0.0 V1103.12 V (2298.18%)334375.0 WDrop High
25 mm²101 A78 A428.0 V (891.67%)0.0 V706.0 V (1470.83%)214000.0 WDrop High
35 mm²125 A97 A305.71 V (636.9%)0.0 V504.29 V (1050.6%)152857.1 WDrop High
50 mm²151 A118 A214.0 V (445.83%)0.0 V353.0 V (735.42%)107000.0 WDrop High
70 mm²192 A150 A152.86 V (318.45%)0.0 V252.14 V (525.3%)76428.6 WDrop High
95 mm²232 A181 A112.63 V (234.65%)0.0 V185.79 V (387.06%)56315.8 WDrop High
120 mm²269 A210 A89.17 V (185.76%)0.0 V147.08 V (306.42%)44583.3 WDrop High
150 mm²309 A241 A71.33 V (148.61%)0.0 V117.67 V (245.14%)35666.7 WDrop High
185 mm²353 A275 A57.84 V (120.5%)0.0 V95.41 V (198.76%)28918.9 WDrop High
240 mm²415 A324 A44.58 V (92.88%)3.4 V73.54 V (153.21%)22291.7 WDrop High
300 mm²477 A372 A35.67 V (74.31%)12.3 V58.83 V (122.57%)17833.3 WDrop High
400 mm²570 A445 A26.75 V (55.73%)21.2 V44.12 V (91.93%)13375.0 WDrop High

FAQ — 500 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 500A at 500 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 19× 400 mm² copper cable for 500A over 500m at 48V (voltage drop: 1.41V or 2.93%).

What is the power capacity of 500A at 48V?

At unity power factor, 500A at 48V supports 24.0 kW with a standard 500A circuit breaker.