125 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.03V (22.98%)
Voltage at Load46.7 VLine Loss: 167.2 W
Max Power & Breaker6.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1783.33 V (3715.28%)0.0 V2941.67 V (6128.47%)222916.7 WDrop High
2.5 mm²24 A18 A1070.0 V (2229.17%)0.0 V1765.0 V (3677.08%)133750.0 WDrop High
4 mm²32 A25 A668.75 V (1393.23%)0.0 V1103.12 V (2298.18%)83593.8 WDrop High
6 mm²41 A32 A445.83 V (928.82%)0.0 V735.42 V (1532.12%)55729.2 WDrop High
10 mm²57 A44 A267.5 V (557.29%)0.0 V441.25 V (919.27%)33437.5 WDrop High
16 mm²76 A59 A167.19 V (348.31%)0.0 V275.78 V (574.54%)20898.4 WDrop High
25 mm²101 A78 A107.0 V (222.92%)0.0 V176.5 V (367.71%)13375.0 WDrop High
35 mm²125 A97 A76.43 V (159.23%)0.0 V126.07 V (262.65%)9553.6 WDrop High
50 mm²151 A118 A53.5 V (111.46%)0.0 V88.25 V (183.85%)6687.5 WDrop High
70 mm²192 A150 A38.21 V (79.61%)9.8 V63.04 V (131.32%)4776.8 WDrop High
95 mm²232 A181 A28.16 V (58.66%)19.8 V46.45 V (96.77%)3519.7 WDrop High
120 mm²269 A210 A22.29 V (46.44%)25.7 V36.77 V (76.61%)2786.5 WDrop High
150 mm²309 A241 A17.83 V (37.15%)30.2 V29.42 V (61.28%)2229.2 WDrop High
185 mm²353 A275 A14.46 V (30.12%)33.5 V23.85 V (49.69%)1807.4 WDrop High
240 mm²415 A324 A11.15 V (23.22%)36.9 V18.39 V (38.3%)1393.2 WDrop High
300 mm²477 A372 A8.92 V (18.58%)39.1 V14.71 V (30.64%)1114.6 WDrop High
400 mm²570 A445 A6.69 V (13.93%)41.3 V11.03 V (22.98%)835.9 WDrop High

FAQ — 125 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 125A at 500 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 125A over 500m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 125A at 48V?

At unity power factor, 125A at 48V supports 6.0 kW with a standard 125A circuit breaker.