60 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 60 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 9.53V (2.3%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.01V (2.65%)
Voltage at Load405.5 VLine Loss: 990.5 W
Max Power & Breaker43.13 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A222.4 V (53.59%)192.6 V366.85 V (88.4%)23112.0 WDrop High
2.5 mm²24 A18 A133.44 V (32.15%)281.6 V220.11 V (53.04%)13867.2 WDrop High
4 mm²32 A25 A83.4 V (20.1%)331.6 V137.57 V (33.15%)8667.0 WDrop High
6 mm²41 A32 A55.6 V (13.4%)359.4 V91.71 V (22.1%)5778.0 WDrop High
10 mm²57 A44 A33.36 V (8.04%)381.6 V55.03 V (13.26%)3466.8 WDrop High
16 mm²76 A59 A20.85 V (5.02%)394.2 V34.39 V (8.29%)2166.8 WDrop High
25 mm²101 A78 A13.34 V (3.22%)401.7 V22.01 V (5.3%)1386.7 W~ ≤5%
35 mm²125 A97 A9.53 V (2.3%)405.5 V15.72 V (3.79%)990.5 W✓ OK (≤3%)
50 mm²151 A118 A6.67 V (1.61%)408.3 V11.01 V (2.65%)693.4 W✓ OK (≤3%)
70 mm²192 A150 A4.77 V (1.15%)410.2 V7.86 V (1.89%)495.3 W✓ OK (≤3%)
95 mm²232 A181 A3.51 V (0.85%)411.5 V5.79 V (1.4%)364.9 W✓ OK (≤3%)
120 mm²269 A210 A2.78 V (0.67%)412.2 V4.59 V (1.1%)288.9 W✓ OK (≤3%)
150 mm²309 A241 A2.22 V (0.54%)412.8 V3.67 V (0.88%)231.1 W✓ OK (≤3%)
185 mm²353 A275 A1.8 V (0.43%)413.2 V2.97 V (0.72%)187.4 W✓ OK (≤3%)
240 mm²415 A324 A1.39 V (0.33%)413.6 V2.29 V (0.55%)144.4 W✓ OK (≤3%)
300 mm²477 A372 A1.11 V (0.27%)413.9 V1.83 V (0.44%)115.6 W✓ OK (≤3%)
400 mm²570 A445 A0.83 V (0.2%)414.2 V1.38 V (0.33%)86.7 W✓ OK (≤3%)

FAQ — 60 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 60A at 150 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 60A over 150m at 415V (voltage drop: 9.53V or 2.3%).

What is the power capacity of 60A at 415V?

At unity power factor, 60A at 415V supports 43.13 kW with a standard 60A circuit breaker.