60 Amp Cable Size at 350 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 60 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.18V (2.69%)
Voltage at Load224.0 VLine Loss: 359.5 W
Max Power & Breaker13.8 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A599.2 V (260.52%)0.0 V988.4 V (429.74%)35952.0 WDrop High
2.5 mm²24 A18 A359.52 V (156.31%)0.0 V593.04 V (257.84%)21571.2 WDrop High
4 mm²32 A25 A224.7 V (97.7%)5.3 V370.65 V (161.15%)13482.0 WDrop High
6 mm²41 A32 A149.8 V (65.13%)80.2 V247.1 V (107.43%)8988.0 WDrop High
10 mm²57 A44 A89.88 V (39.08%)140.1 V148.26 V (64.46%)5392.8 WDrop High
16 mm²76 A59 A56.17 V (24.42%)173.8 V92.66 V (40.29%)3370.5 WDrop High
25 mm²101 A78 A35.95 V (15.63%)194.0 V59.3 V (25.78%)2157.1 WDrop High
35 mm²125 A97 A25.68 V (11.17%)204.3 V42.36 V (18.42%)1540.8 WDrop High
50 mm²151 A118 A17.98 V (7.82%)212.0 V29.65 V (12.89%)1078.6 WDrop High
70 mm²192 A150 A12.84 V (5.58%)217.2 V21.18 V (9.21%)770.4 WDrop High
95 mm²232 A181 A9.46 V (4.11%)220.5 V15.61 V (6.79%)567.7 W~ ≤5%
120 mm²269 A210 A7.49 V (3.26%)222.5 V12.35 V (5.37%)449.4 W~ ≤5%
150 mm²309 A241 A5.99 V (2.61%)224.0 V9.88 V (4.3%)359.5 W✓ OK (≤3%)
185 mm²353 A275 A4.86 V (2.11%)225.1 V8.01 V (3.48%)291.5 W✓ OK (≤3%)
240 mm²415 A324 A3.74 V (1.63%)226.3 V6.18 V (2.69%)224.7 W✓ OK (≤3%)
300 mm²477 A372 A3.0 V (1.3%)227.0 V4.94 V (2.15%)179.8 W✓ OK (≤3%)
400 mm²570 A445 A2.25 V (0.98%)227.8 V3.71 V (1.61%)134.8 W✓ OK (≤3%)

FAQ — 60 Amp Cable Size at 350 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 60A at 350 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 60A over 350m at 230V (voltage drop: 5.99V or 2.61%).

What is the power capacity of 60A at 230V?

At unity power factor, 60A at 230V supports 13.8 kW with a standard 60A circuit breaker.