25 Amp Cable Size at 350 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 6.5V (2.83%)
Voltage at Load224.7 VLine Loss: 133.7 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A249.67 V (108.55%)0.0 V411.83 V (179.06%)6241.7 WDrop High
2.5 mm²24 A18 A149.8 V (65.13%)80.2 V247.1 V (107.43%)3745.0 WDrop High
4 mm²32 A25 A93.62 V (40.71%)136.4 V154.44 V (67.15%)2340.6 WDrop High
6 mm²41 A32 A62.42 V (27.14%)167.6 V102.96 V (44.76%)1560.4 WDrop High
10 mm²57 A44 A37.45 V (16.28%)192.6 V61.77 V (26.86%)936.2 WDrop High
16 mm²76 A59 A23.41 V (10.18%)206.6 V38.61 V (16.79%)585.2 WDrop High
25 mm²101 A78 A14.98 V (6.51%)215.0 V24.71 V (10.74%)374.5 WDrop High
35 mm²125 A97 A10.7 V (4.65%)219.3 V17.65 V (7.67%)267.5 W~ ≤5%
50 mm²151 A118 A7.49 V (3.26%)222.5 V12.35 V (5.37%)187.2 W~ ≤5%
70 mm²192 A150 A5.35 V (2.33%)224.7 V8.82 V (3.84%)133.7 W✓ OK (≤3%)
95 mm²232 A181 A3.94 V (1.71%)226.1 V6.5 V (2.83%)98.6 W✓ OK (≤3%)
120 mm²269 A210 A3.12 V (1.36%)226.9 V5.15 V (2.24%)78.0 W✓ OK (≤3%)
150 mm²309 A241 A2.5 V (1.09%)227.5 V4.12 V (1.79%)62.4 W✓ OK (≤3%)
185 mm²353 A275 A2.02 V (0.88%)228.0 V3.34 V (1.45%)50.6 W✓ OK (≤3%)
240 mm²415 A324 A1.56 V (0.68%)228.4 V2.57 V (1.12%)39.0 W✓ OK (≤3%)
300 mm²477 A372 A1.25 V (0.54%)228.8 V2.06 V (0.9%)31.2 W✓ OK (≤3%)
400 mm²570 A445 A0.94 V (0.41%)229.1 V1.54 V (0.67%)23.4 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 350 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 25A at 350 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 25A over 350m at 230V (voltage drop: 5.35V or 2.33%).

What is the power capacity of 25A at 230V?

At unity power factor, 25A at 230V supports 5.75 kW with a standard 25A circuit breaker.