600 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.16V (0.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.53V (2.21%)
Voltage at Load23.8 VLine Loss: 96.3 W
Max Power & Breaker14.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A85.6 V (356.67%)0.0 V141.2 V (588.33%)51360.0 WDrop High
2.5 mm²24 A18 A51.36 V (214.0%)0.0 V84.72 V (353.0%)30816.0 WDrop High
4 mm²32 A25 A32.1 V (133.75%)0.0 V52.95 V (220.62%)19260.0 WDrop High
6 mm²41 A32 A21.4 V (89.17%)2.6 V35.3 V (147.08%)12840.0 WDrop High
10 mm²57 A44 A12.84 V (53.5%)11.2 V21.18 V (88.25%)7704.0 WDrop High
16 mm²76 A59 A8.03 V (33.44%)16.0 V13.24 V (55.16%)4815.0 WDrop High
25 mm²101 A78 A5.14 V (21.4%)18.9 V8.47 V (35.3%)3081.6 WDrop High
35 mm²125 A97 A3.67 V (15.29%)20.3 V6.05 V (25.21%)2201.1 WDrop High
50 mm²151 A118 A2.57 V (10.7%)21.4 V4.24 V (17.65%)1540.8 WDrop High
70 mm²192 A150 A1.83 V (7.64%)22.2 V3.03 V (12.61%)1100.6 WDrop High
95 mm²232 A181 A1.35 V (5.63%)22.6 V2.23 V (9.29%)810.9 WDrop High
120 mm²269 A210 A1.07 V (4.46%)22.9 V1.76 V (7.35%)642.0 WDrop High
150 mm²309 A241 A0.86 V (3.57%)23.1 V1.41 V (5.88%)513.6 WDrop High
185 mm²353 A275 A0.69 V (2.89%)23.3 V1.14 V (4.77%)416.4 WDrop High
240 mm²415 A324 A0.54 V (2.23%)23.5 V0.88 V (3.68%)321.0 WDrop High
300 mm²477 A372 A0.43 V (1.78%)23.6 V0.71 V (2.94%)256.8 WDrop High
400 mm²570 A445 A0.32 V (1.34%)23.7 V0.53 V (2.21%)192.6 WDrop High

FAQ — 600 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 600A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 5m at 24V (voltage drop: 0.16V or 0.67%).

What is the power capacity of 600A at 24V?

At unity power factor, 600A at 24V supports 14.4 kW with a standard 600A circuit breaker.