600 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 70 m (229.7 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.95V (0.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.42V (1.55%)
Voltage at Load413.1 VLine Loss: 2022.3 W
Max Power & Breaker431.28 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1037.84 V (250.08%) | 0.0 V | 1711.96 V (412.52%) | 1078560.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 622.71 V (150.05%) | 0.0 V | 1027.18 V (247.51%) | 647136.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 389.19 V (93.78%) | 25.8 V | 641.98 V (154.7%) | 404460.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 259.46 V (62.52%) | 155.5 V | 427.99 V (103.13%) | 269640.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 155.68 V (37.51%) | 259.3 V | 256.79 V (61.88%) | 161784.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 97.3 V (23.45%) | 317.7 V | 160.5 V (38.67%) | 101115.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 62.27 V (15.0%) | 352.7 V | 102.72 V (24.75%) | 64713.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 44.48 V (10.72%) | 370.5 V | 73.37 V (17.68%) | 46224.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 31.14 V (7.5%) | 383.9 V | 51.36 V (12.38%) | 32356.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 22.24 V (5.36%) | 392.8 V | 36.68 V (8.84%) | 23112.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 16.39 V (3.95%) | 398.6 V | 27.03 V (6.51%) | 17029.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 12.97 V (3.13%) | 402.0 V | 21.4 V (5.16%) | 13482.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 10.38 V (2.5%) | 404.6 V | 17.12 V (4.13%) | 10785.6 W | Drop High |
| 185 mm² | 353 A | 275 A | 8.41 V (2.03%) | 406.6 V | 13.88 V (3.34%) | 8745.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 6.49 V (1.56%) | 408.5 V | 10.7 V (2.58%) | 6741.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 5.19 V (1.25%) | 409.8 V | 8.56 V (2.06%) | 5392.8 W | Drop High |
| 400 mm² | 570 A | 445 A | 3.89 V (0.94%) | 411.1 V | 6.42 V (1.55%) | 4044.6 W | Drop High |
FAQ — 600 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 600A at 70 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 70m at 415V (voltage drop: 1.95V or 0.47%).
What is the power capacity of 600A at 415V?
At unity power factor, 600A at 415V supports 431.28 kW with a standard 600A circuit breaker.
Related Lengths & Currents (415V)
600A · 5m (415V)600A · 10m (415V)600A · 15m (415V)600A · 20m (415V)600A · 25m (415V)600A · 30m (415V)600A · 35m (415V)600A · 40m (415V)600A · 45m (415V)600A · 50m (415V)600A · 60m (415V)10A · 70m (415V)16A · 70m (415V)20A · 70m (415V)25A · 70m (415V)32A · 70m (415V)40A · 70m (415V)50A · 70m (415V)63A · 70m (415V)80A · 70m (415V)100A · 70m (415V)125A · 70m (415V)160A · 70m (415V)200A · 70m (415V)