10 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 10.38V (2.5%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 10.7V (2.58%)
Voltage at Load404.6 VLine Loss: 179.8 W
Max Power & Breaker7.19 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.3 V (4.17%)397.7 V28.53 V (6.88%)299.6 W~ ≤5%
2.5 mm²24 A18 A10.38 V (2.5%)404.6 V17.12 V (4.13%)179.8 W✓ OK (≤3%)
4 mm²32 A25 A6.49 V (1.56%)408.5 V10.7 V (2.58%)112.3 W✓ OK (≤3%)
6 mm²41 A32 A4.32 V (1.04%)410.7 V7.13 V (1.72%)74.9 W✓ OK (≤3%)
10 mm²57 A44 A2.59 V (0.63%)412.4 V4.28 V (1.03%)44.9 W✓ OK (≤3%)
16 mm²76 A59 A1.62 V (0.39%)413.4 V2.67 V (0.64%)28.1 W✓ OK (≤3%)
25 mm²101 A78 A1.04 V (0.25%)414.0 V1.71 V (0.41%)18.0 W✓ OK (≤3%)
35 mm²125 A97 A0.74 V (0.18%)414.3 V1.22 V (0.29%)12.8 W✓ OK (≤3%)
50 mm²151 A118 A0.52 V (0.13%)414.5 V0.86 V (0.21%)9.0 W✓ OK (≤3%)
70 mm²192 A150 A0.37 V (0.09%)414.6 V0.61 V (0.15%)6.4 W✓ OK (≤3%)
95 mm²232 A181 A0.27 V (0.07%)414.7 V0.45 V (0.11%)4.7 W✓ OK (≤3%)
120 mm²269 A210 A0.22 V (0.05%)414.8 V0.36 V (0.09%)3.7 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.04%)414.8 V0.29 V (0.07%)3.0 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.03%)414.9 V0.23 V (0.06%)2.4 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.03%)414.9 V0.18 V (0.04%)1.9 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.02%)414.9 V0.14 V (0.03%)1.5 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.02%)414.9 V0.11 V (0.03%)1.1 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 10A at 70 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 10A over 70m at 415V (voltage drop: 10.38V or 2.5%).

What is the power capacity of 10A at 415V?

At unity power factor, 10A at 415V supports 7.19 kW with a standard 10A circuit breaker.