63 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 6.47V (2.81%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.62V (2.44%)
Voltage at Load223.5 VLine Loss: 407.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A215.71 V (93.79%)14.3 V355.82 V (154.71%)13589.9 WDrop High
2.5 mm²24 A18 A129.43 V (56.27%)100.6 V213.49 V (92.82%)8153.9 WDrop High
4 mm²32 A25 A80.89 V (35.17%)149.1 V133.43 V (58.01%)5096.2 WDrop High
6 mm²41 A32 A53.93 V (23.45%)176.1 V88.96 V (38.68%)3397.5 WDrop High
10 mm²57 A44 A32.36 V (14.07%)197.6 V53.37 V (23.21%)2038.5 WDrop High
16 mm²76 A59 A20.22 V (8.79%)209.8 V33.36 V (14.5%)1274.0 WDrop High
25 mm²101 A78 A12.94 V (5.63%)217.1 V21.35 V (9.28%)815.4 WDrop High
35 mm²125 A97 A9.24 V (4.02%)220.8 V15.25 V (6.63%)582.4 W~ ≤5%
50 mm²151 A118 A6.47 V (2.81%)223.5 V10.67 V (4.64%)407.7 W✓ OK (≤3%)
70 mm²192 A150 A4.62 V (2.01%)225.4 V7.62 V (3.32%)291.2 W✓ OK (≤3%)
95 mm²232 A181 A3.41 V (1.48%)226.6 V5.62 V (2.44%)214.6 W✓ OK (≤3%)
120 mm²269 A210 A2.7 V (1.17%)227.3 V4.45 V (1.93%)169.9 W✓ OK (≤3%)
150 mm²309 A241 A2.16 V (0.94%)227.8 V3.56 V (1.55%)135.9 W✓ OK (≤3%)
185 mm²353 A275 A1.75 V (0.76%)228.3 V2.89 V (1.25%)110.2 W✓ OK (≤3%)
240 mm²415 A324 A1.35 V (0.59%)228.7 V2.22 V (0.97%)84.9 W✓ OK (≤3%)
300 mm²477 A372 A1.08 V (0.47%)228.9 V1.78 V (0.77%)67.9 W✓ OK (≤3%)
400 mm²570 A445 A0.81 V (0.35%)229.2 V1.33 V (0.58%)51.0 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 63A at 120 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 63A over 120m at 230V (voltage drop: 6.47V or 2.81%).

What is the power capacity of 63A at 230V?

At unity power factor, 63A at 230V supports 14.49 kW with a standard 63A circuit breaker.