32 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 6.57V (2.86%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.42V (2.36%)
Voltage at Load223.4 VLine Loss: 210.4 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A109.57 V (47.64%)120.4 V180.74 V (78.58%)3506.2 WDrop High
2.5 mm²24 A18 A65.74 V (28.58%)164.3 V108.44 V (47.15%)2103.7 WDrop High
4 mm²32 A25 A41.09 V (17.86%)188.9 V67.78 V (29.47%)1314.8 WDrop High
6 mm²41 A32 A27.39 V (11.91%)202.6 V45.18 V (19.65%)876.5 WDrop High
10 mm²57 A44 A16.44 V (7.15%)213.6 V27.11 V (11.79%)525.9 WDrop High
16 mm²76 A59 A10.27 V (4.47%)219.7 V16.94 V (7.37%)328.7 W~ ≤5%
25 mm²101 A78 A6.57 V (2.86%)223.4 V10.84 V (4.71%)210.4 W✓ OK (≤3%)
35 mm²125 A97 A4.7 V (2.04%)225.3 V7.75 V (3.37%)150.3 W✓ OK (≤3%)
50 mm²151 A118 A3.29 V (1.43%)226.7 V5.42 V (2.36%)105.2 W✓ OK (≤3%)
70 mm²192 A150 A2.35 V (1.02%)227.7 V3.87 V (1.68%)75.1 W✓ OK (≤3%)
95 mm²232 A181 A1.73 V (0.75%)228.3 V2.85 V (1.24%)55.4 W✓ OK (≤3%)
120 mm²269 A210 A1.37 V (0.6%)228.6 V2.26 V (0.98%)43.8 W✓ OK (≤3%)
150 mm²309 A241 A1.1 V (0.48%)228.9 V1.81 V (0.79%)35.1 W✓ OK (≤3%)
185 mm²353 A275 A0.89 V (0.39%)229.1 V1.47 V (0.64%)28.4 W✓ OK (≤3%)
240 mm²415 A324 A0.68 V (0.3%)229.3 V1.13 V (0.49%)21.9 W✓ OK (≤3%)
300 mm²477 A372 A0.55 V (0.24%)229.5 V0.9 V (0.39%)17.5 W✓ OK (≤3%)
400 mm²570 A445 A0.41 V (0.18%)229.6 V0.68 V (0.29%)13.1 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 32A at 120 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 32A over 120m at 230V (voltage drop: 6.57V or 2.86%).

What is the power capacity of 32A at 230V?

At unity power factor, 32A at 230V supports 7.36 kW with a standard 32A circuit breaker.