650 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 650 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.41V (0.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.95V (1.99%)
Voltage at Load397.6 VLine Loss: 2712.4 W
Max Power & Breaker450.33 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1284.95 V (321.24%)0.0 V2119.57 V (529.89%)1446640.0 WDrop High
2.5 mm²24 A18 A770.97 V (192.74%)0.0 V1271.74 V (317.94%)867984.0 WDrop High
4 mm²32 A25 A481.86 V (120.46%)0.0 V794.84 V (198.71%)542490.0 WDrop High
6 mm²41 A32 A321.24 V (80.31%)78.8 V529.89 V (132.47%)361660.0 WDrop High
10 mm²57 A44 A192.74 V (48.19%)207.3 V317.94 V (79.48%)216996.0 WDrop High
16 mm²76 A59 A120.46 V (30.12%)279.5 V198.71 V (49.68%)135622.5 WDrop High
25 mm²101 A78 A77.1 V (19.27%)322.9 V127.17 V (31.79%)86798.4 WDrop High
35 mm²125 A97 A55.07 V (13.77%)344.9 V90.84 V (22.71%)61998.9 WDrop High
50 mm²151 A118 A38.55 V (9.64%)361.5 V63.59 V (15.9%)43399.2 WDrop High
70 mm²192 A150 A27.53 V (6.88%)372.5 V45.42 V (11.35%)30999.4 WDrop High
95 mm²232 A181 A20.29 V (5.07%)379.7 V33.47 V (8.37%)22841.7 WDrop High
120 mm²269 A210 A16.06 V (4.02%)383.9 V26.49 V (6.62%)18083.0 WDrop High
150 mm²309 A241 A12.85 V (3.21%)387.2 V21.2 V (5.3%)14466.4 WDrop High
185 mm²353 A275 A10.42 V (2.6%)389.6 V17.19 V (4.3%)11729.5 WDrop High
240 mm²415 A324 A8.03 V (2.01%)392.0 V13.25 V (3.31%)9041.5 WDrop High
300 mm²477 A372 A6.42 V (1.61%)393.6 V10.6 V (2.65%)7233.2 WDrop High
400 mm²570 A445 A4.82 V (1.2%)395.2 V7.95 V (1.99%)5424.9 WDrop High

FAQ — 650 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 650A at 80 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 650A over 80m at 400V (voltage drop: 2.41V or 0.6%).

What is the power capacity of 650A at 400V?

At unity power factor, 650A at 400V supports 450.33 kW with a standard 700A circuit breaker.