⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

700 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.56V (1.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.85V (3.86%)
Voltage at Load47.4 VLine Loss: 393.2 W
Max Power & Breaker33.6 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A299.6 V (624.17%)0.0 V494.2 V (1029.58%)209720.0 WDrop High
2.5 mm²24 A18 A179.76 V (374.5%)0.0 V296.52 V (617.75%)125832.0 WDrop High
4 mm²32 A25 A112.35 V (234.06%)0.0 V185.32 V (386.09%)78645.0 WDrop High
6 mm²41 A32 A74.9 V (156.04%)0.0 V123.55 V (257.4%)52430.0 WDrop High
10 mm²57 A44 A44.94 V (93.63%)3.1 V74.13 V (154.44%)31458.0 WDrop High
16 mm²76 A59 A28.09 V (58.52%)19.9 V46.33 V (96.52%)19661.2 WDrop High
25 mm²101 A78 A17.98 V (37.45%)30.0 V29.65 V (61.77%)12583.2 WDrop High
35 mm²125 A97 A12.84 V (26.75%)35.2 V21.18 V (44.12%)8988.0 WDrop High
50 mm²151 A118 A8.99 V (18.73%)39.0 V14.83 V (30.89%)6291.6 WDrop High
70 mm²192 A150 A6.42 V (13.38%)41.6 V10.59 V (22.06%)4494.0 WDrop High
95 mm²232 A181 A4.73 V (9.86%)43.3 V7.8 V (16.26%)3311.4 WDrop High
120 mm²269 A210 A3.74 V (7.8%)44.3 V6.18 V (12.87%)2621.5 WDrop High
150 mm²309 A241 A3.0 V (6.24%)45.0 V4.94 V (10.3%)2097.2 WDrop High
185 mm²353 A275 A2.43 V (5.06%)45.6 V4.01 V (8.35%)1700.4 WDrop High
240 mm²415 A324 A1.87 V (3.9%)46.1 V3.09 V (6.43%)1310.8 WDrop High
300 mm²477 A372 A1.5 V (3.12%)46.5 V2.47 V (5.15%)1048.6 WDrop High
400 mm²570 A445 A1.12 V (2.34%)46.9 V1.85 V (3.86%)786.5 WDrop High

FAQ — 700 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 700A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 15m at 48V (voltage drop: 0.56V or 1.17%).

What is the power capacity of 700A at 48V?

At unity power factor, 700A at 48V supports 33.6 kW with a standard 700A circuit breaker.