750 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.2V (0.83%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.66V (2.76%)
Voltage at Load23.8 VLine Loss: 150.4 W
Max Power & Breaker18.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A107.0 V (445.83%)0.0 V176.5 V (735.42%)80250.0 WDrop High
2.5 mm²24 A18 A64.2 V (267.5%)0.0 V105.9 V (441.25%)48150.0 WDrop High
4 mm²32 A25 A40.12 V (167.19%)0.0 V66.19 V (275.78%)30093.8 WDrop High
6 mm²41 A32 A26.75 V (111.46%)0.0 V44.12 V (183.85%)20062.5 WDrop High
10 mm²57 A44 A16.05 V (66.88%)7.9 V26.47 V (110.31%)12037.5 WDrop High
16 mm²76 A59 A10.03 V (41.8%)14.0 V16.55 V (68.95%)7523.4 WDrop High
25 mm²101 A78 A6.42 V (26.75%)17.6 V10.59 V (44.12%)4815.0 WDrop High
35 mm²125 A97 A4.59 V (19.11%)19.4 V7.56 V (31.52%)3439.3 WDrop High
50 mm²151 A118 A3.21 V (13.38%)20.8 V5.29 V (22.06%)2407.5 WDrop High
70 mm²192 A150 A2.29 V (9.55%)21.7 V3.78 V (15.76%)1719.6 WDrop High
95 mm²232 A181 A1.69 V (7.04%)22.3 V2.79 V (11.61%)1267.1 WDrop High
120 mm²269 A210 A1.34 V (5.57%)22.7 V2.21 V (9.19%)1003.1 WDrop High
150 mm²309 A241 A1.07 V (4.46%)22.9 V1.76 V (7.35%)802.5 WDrop High
185 mm²353 A275 A0.87 V (3.61%)23.1 V1.43 V (5.96%)650.7 WDrop High
240 mm²415 A324 A0.67 V (2.79%)23.3 V1.1 V (4.6%)501.6 WDrop High
300 mm²477 A372 A0.53 V (2.23%)23.5 V0.88 V (3.68%)401.2 WDrop High
400 mm²570 A445 A0.4 V (1.67%)23.6 V0.66 V (2.76%)300.9 WDrop High

FAQ — 750 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 750A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 5m at 24V (voltage drop: 0.2V or 0.83%).

What is the power capacity of 750A at 24V?

At unity power factor, 750A at 24V supports 18.0 kW with a standard 800A circuit breaker.