⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

80 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 1.78V (0.43%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 2.1V (0.51%)
Voltage at Load413.2 VLine Loss: 246.5 W
Max Power & Breaker57.5 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A29.65 V (7.15%)385.3 V48.91 V (11.79%)4108.8 WDrop High
2.5 mm²24 A18 A17.79 V (4.29%)397.2 V29.35 V (7.07%)2465.3 WDrop High
4 mm²32 A25 A11.12 V (2.68%)403.9 V18.34 V (4.42%)1540.8 WDrop High
6 mm²41 A32 A7.41 V (1.79%)407.6 V12.23 V (2.95%)1027.2 WDrop High
10 mm²57 A44 A4.45 V (1.07%)410.6 V7.34 V (1.77%)616.3 WDrop High
16 mm²76 A59 A2.78 V (0.67%)412.2 V4.59 V (1.1%)385.2 WDrop High
25 mm²101 A78 A1.78 V (0.43%)413.2 V2.93 V (0.71%)246.5 W✓ OK (≤3%)
35 mm²125 A97 A1.27 V (0.31%)413.7 V2.1 V (0.51%)176.1 W✓ OK (≤3%)
50 mm²151 A118 A0.89 V (0.21%)414.1 V1.47 V (0.35%)123.3 W✓ OK (≤3%)
70 mm²192 A150 A0.64 V (0.15%)414.4 V1.05 V (0.25%)88.0 W✓ OK (≤3%)
95 mm²232 A181 A0.47 V (0.11%)414.5 V0.77 V (0.19%)64.9 W✓ OK (≤3%)
120 mm²269 A210 A0.37 V (0.09%)414.6 V0.61 V (0.15%)51.4 W✓ OK (≤3%)
150 mm²309 A241 A0.3 V (0.07%)414.7 V0.49 V (0.12%)41.1 W✓ OK (≤3%)
185 mm²353 A275 A0.24 V (0.06%)414.8 V0.4 V (0.1%)33.3 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.04%)414.8 V0.31 V (0.07%)25.7 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.04%)414.9 V0.24 V (0.06%)20.5 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.03%)414.9 V0.18 V (0.04%)15.4 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 80A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 15m at 415V (voltage drop: 1.78V or 0.43%).

What is the power capacity of 80A at 415V?

At unity power factor, 80A at 415V supports 57.5 kW with a standard 80A circuit breaker.