63 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 2.19V (0.53%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 2.31V (0.56%)
Voltage at Load412.8 VLine Loss: 238.9 W
Max Power & Breaker45.28 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A23.35 V (5.63%)391.6 V38.52 V (9.28%)2548.1 WDrop High
2.5 mm²24 A18 A14.01 V (3.38%)401.0 V23.11 V (5.57%)1528.9 WDrop High
4 mm²32 A25 A8.76 V (2.11%)406.2 V14.44 V (3.48%)955.5 WDrop High
6 mm²41 A32 A5.84 V (1.41%)409.2 V9.63 V (2.32%)637.0 WDrop High
10 mm²57 A44 A3.5 V (0.84%)411.5 V5.78 V (1.39%)382.2 WDrop High
16 mm²76 A59 A2.19 V (0.53%)412.8 V3.61 V (0.87%)238.9 W✓ OK (≤3%)
25 mm²101 A78 A1.4 V (0.34%)413.6 V2.31 V (0.56%)152.9 W✓ OK (≤3%)
35 mm²125 A97 A1.0 V (0.24%)414.0 V1.65 V (0.4%)109.2 W✓ OK (≤3%)
50 mm²151 A118 A0.7 V (0.17%)414.3 V1.16 V (0.28%)76.4 W✓ OK (≤3%)
70 mm²192 A150 A0.5 V (0.12%)414.5 V0.83 V (0.2%)54.6 W✓ OK (≤3%)
95 mm²232 A181 A0.37 V (0.09%)414.6 V0.61 V (0.15%)40.2 W✓ OK (≤3%)
120 mm²269 A210 A0.29 V (0.07%)414.7 V0.48 V (0.12%)31.9 W✓ OK (≤3%)
150 mm²309 A241 A0.23 V (0.06%)414.8 V0.39 V (0.09%)25.5 W✓ OK (≤3%)
185 mm²353 A275 A0.19 V (0.05%)414.8 V0.31 V (0.08%)20.7 W✓ OK (≤3%)
240 mm²415 A324 A0.15 V (0.04%)414.9 V0.24 V (0.06%)15.9 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.03%)414.9 V0.19 V (0.05%)12.7 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.02%)414.9 V0.14 V (0.03%)9.6 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 63A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 63A over 15m at 415V (voltage drop: 2.19V or 0.53%).

What is the power capacity of 63A at 415V?

At unity power factor, 63A at 415V supports 45.28 kW with a standard 63A circuit breaker.