⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

80 Amp Cable Size at 40 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 5.48V (2.38%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 6.45V (2.81%)
Voltage at Load224.5 VLine Loss: 438.3 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A91.31 V (39.7%)138.7 V150.61 V (65.48%)7304.5 WDrop High
2.5 mm²24 A18 A54.78 V (23.82%)175.2 V90.37 V (39.29%)4382.7 WDrop High
4 mm²32 A25 A34.24 V (14.89%)195.8 V56.48 V (24.56%)2739.2 WDrop High
6 mm²41 A32 A22.83 V (9.92%)207.2 V37.65 V (16.37%)1826.1 WDrop High
10 mm²57 A44 A13.7 V (5.95%)216.3 V22.59 V (9.82%)1095.7 WDrop High
16 mm²76 A59 A8.56 V (3.72%)221.4 V14.12 V (6.14%)684.8 WDrop High
25 mm²101 A78 A5.48 V (2.38%)224.5 V9.04 V (3.93%)438.3 W✓ OK (≤3%)
35 mm²125 A97 A3.91 V (1.7%)226.1 V6.45 V (2.81%)313.1 W✓ OK (≤3%)
50 mm²151 A118 A2.74 V (1.19%)227.3 V4.52 V (1.96%)219.1 W✓ OK (≤3%)
70 mm²192 A150 A1.96 V (0.85%)228.0 V3.23 V (1.4%)156.5 W✓ OK (≤3%)
95 mm²232 A181 A1.44 V (0.63%)228.6 V2.38 V (1.03%)115.3 W✓ OK (≤3%)
120 mm²269 A210 A1.14 V (0.5%)228.9 V1.88 V (0.82%)91.3 W✓ OK (≤3%)
150 mm²309 A241 A0.91 V (0.4%)229.1 V1.51 V (0.65%)73.0 W✓ OK (≤3%)
185 mm²353 A275 A0.74 V (0.32%)229.3 V1.22 V (0.53%)59.2 W✓ OK (≤3%)
240 mm²415 A324 A0.57 V (0.25%)229.4 V0.94 V (0.41%)45.7 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.2%)229.5 V0.75 V (0.33%)36.5 W✓ OK (≤3%)
400 mm²570 A445 A0.34 V (0.15%)229.7 V0.56 V (0.25%)27.4 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 40 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 80A at 40 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 40m at 230V (voltage drop: 5.48V or 2.38%).

What is the power capacity of 80A at 230V?

At unity power factor, 80A at 230V supports 18.4 kW with a standard 80A circuit breaker.