16 Amp Cable Size at 40 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 4.52V (1.96%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.26 V (7.94%)211.7 V30.12 V (13.1%)292.2 WDrop High
2.5 mm²24 A18 A10.96 V (4.76%)219.0 V18.07 V (7.86%)175.3 W~ ≤5%
4 mm²32 A25 A6.85 V (2.98%)223.2 V11.3 V (4.91%)109.6 W✓ OK (≤3%)
6 mm²41 A32 A4.57 V (1.98%)225.4 V7.53 V (3.27%)73.0 W✓ OK (≤3%)
10 mm²57 A44 A2.74 V (1.19%)227.3 V4.52 V (1.96%)43.8 W✓ OK (≤3%)
16 mm²76 A59 A1.71 V (0.74%)228.3 V2.82 V (1.23%)27.4 W✓ OK (≤3%)
25 mm²101 A78 A1.1 V (0.48%)228.9 V1.81 V (0.79%)17.5 W✓ OK (≤3%)
35 mm²125 A97 A0.78 V (0.34%)229.2 V1.29 V (0.56%)12.5 W✓ OK (≤3%)
50 mm²151 A118 A0.55 V (0.24%)229.5 V0.9 V (0.39%)8.8 W✓ OK (≤3%)
70 mm²192 A150 A0.39 V (0.17%)229.6 V0.65 V (0.28%)6.3 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.13%)229.7 V0.48 V (0.21%)4.6 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.1%)229.8 V0.38 V (0.16%)3.7 W✓ OK (≤3%)
150 mm²309 A241 A0.18 V (0.08%)229.8 V0.3 V (0.13%)2.9 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.06%)229.9 V0.24 V (0.11%)2.4 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.05%)229.9 V0.19 V (0.08%)1.8 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.04%)229.9 V0.15 V (0.07%)1.5 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.1 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 40 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 16A at 40 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 16A over 40m at 230V (voltage drop: 6.85V or 2.98%).

What is the power capacity of 16A at 230V?

At unity power factor, 16A at 230V supports 3.68 kW with a standard 16A circuit breaker.