⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

800 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.93V (0.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.06V (0.76%)
Voltage at Load399.1 VLine Loss: 1284.0 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A494.21 V (123.55%)0.0 V815.22 V (203.8%)684800.0 WDrop High
2.5 mm²24 A18 A296.53 V (74.13%)103.5 V489.13 V (122.28%)410880.0 WDrop High
4 mm²32 A25 A185.33 V (46.33%)214.7 V305.71 V (76.43%)256800.0 WDrop High
6 mm²41 A32 A123.55 V (30.89%)276.4 V203.8 V (50.95%)171200.0 WDrop High
10 mm²57 A44 A74.13 V (18.53%)325.9 V122.28 V (30.57%)102720.0 WDrop High
16 mm²76 A59 A46.33 V (11.58%)353.7 V76.43 V (19.11%)64200.0 WDrop High
25 mm²101 A78 A29.65 V (7.41%)370.3 V48.91 V (12.23%)41088.0 WDrop High
35 mm²125 A97 A21.18 V (5.3%)378.8 V34.94 V (8.73%)29348.6 WDrop High
50 mm²151 A118 A14.83 V (3.71%)385.2 V24.46 V (6.11%)20544.0 WDrop High
70 mm²192 A150 A10.59 V (2.65%)389.4 V17.47 V (4.37%)14674.3 WDrop High
95 mm²232 A181 A7.8 V (1.95%)392.2 V12.87 V (3.22%)10812.6 WDrop High
120 mm²269 A210 A6.18 V (1.54%)393.8 V10.19 V (2.55%)8560.0 WDrop High
150 mm²309 A241 A4.94 V (1.24%)395.1 V8.15 V (2.04%)6848.0 WDrop High
185 mm²353 A275 A4.01 V (1.0%)396.0 V6.61 V (1.65%)5552.4 WDrop High
240 mm²415 A324 A3.09 V (0.77%)396.9 V5.1 V (1.27%)4280.0 WDrop High
300 mm²477 A372 A2.47 V (0.62%)397.5 V4.08 V (1.02%)3424.0 WDrop High
400 mm²570 A445 A1.85 V (0.46%)398.1 V3.06 V (0.76%)2568.0 WDrop High

FAQ — 800 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 800A at 25 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 25m at 400V (voltage drop: 0.93V or 0.23%).

What is the power capacity of 800A at 400V?

At unity power factor, 800A at 400V supports 554.26 kW with a standard 800A circuit breaker.