800 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.74V (0.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.45V (0.61%)
Voltage at Load399.3 VLine Loss: 1027.2 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A395.37 V (98.84%)4.6 V652.17 V (163.04%)547840.0 WDrop High
2.5 mm²24 A18 A237.22 V (59.31%)162.8 V391.3 V (97.83%)328704.0 WDrop High
4 mm²32 A25 A148.26 V (37.07%)251.7 V244.57 V (61.14%)205440.0 WDrop High
6 mm²41 A32 A98.84 V (24.71%)301.2 V163.04 V (40.76%)136960.0 WDrop High
10 mm²57 A44 A59.31 V (14.83%)340.7 V97.83 V (24.46%)82176.0 WDrop High
16 mm²76 A59 A37.07 V (9.27%)362.9 V61.14 V (15.29%)51360.0 WDrop High
25 mm²101 A78 A23.72 V (5.93%)376.3 V39.13 V (9.78%)32870.4 WDrop High
35 mm²125 A97 A16.94 V (4.24%)383.1 V27.95 V (6.99%)23478.9 WDrop High
50 mm²151 A118 A11.86 V (2.97%)388.1 V19.57 V (4.89%)16435.2 WDrop High
70 mm²192 A150 A8.47 V (2.12%)391.5 V13.98 V (3.49%)11739.4 WDrop High
95 mm²232 A181 A6.24 V (1.56%)393.8 V10.3 V (2.57%)8650.1 WDrop High
120 mm²269 A210 A4.94 V (1.24%)395.1 V8.15 V (2.04%)6848.0 WDrop High
150 mm²309 A241 A3.95 V (0.99%)396.0 V6.52 V (1.63%)5478.4 WDrop High
185 mm²353 A275 A3.21 V (0.8%)396.8 V5.29 V (1.32%)4441.9 WDrop High
240 mm²415 A324 A2.47 V (0.62%)397.5 V4.08 V (1.02%)3424.0 WDrop High
300 mm²477 A372 A1.98 V (0.49%)398.0 V3.26 V (0.82%)2739.2 WDrop High
400 mm²570 A445 A1.48 V (0.37%)398.5 V2.45 V (0.61%)2054.4 WDrop High

FAQ — 800 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 800A at 20 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 20m at 400V (voltage drop: 0.74V or 0.18%).

What is the power capacity of 800A at 400V?

At unity power factor, 800A at 400V supports 554.26 kW with a standard 800A circuit breaker.