90 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 90 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 20.02V (2.9%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 16.51V (2.39%)
Voltage at Load670.0 VLine Loss: 3120.1 W
Max Power & Breaker107.56 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A333.59 V (48.35%)356.4 V550.27 V (79.75%)52002.0 WDrop High
2.5 mm²24 A18 A200.16 V (29.01%)489.8 V330.16 V (47.85%)31201.2 WDrop High
4 mm²32 A25 A125.1 V (18.13%)564.9 V206.35 V (29.91%)19500.8 WDrop High
6 mm²41 A32 A83.4 V (12.09%)606.6 V137.57 V (19.94%)13000.5 WDrop High
10 mm²57 A44 A50.04 V (7.25%)640.0 V82.54 V (11.96%)7800.3 WDrop High
16 mm²76 A59 A31.27 V (4.53%)658.7 V51.59 V (7.48%)4875.2 WDrop High
25 mm²101 A78 A20.02 V (2.9%)670.0 V33.02 V (4.78%)3120.1 W✓ OK (≤3%)
35 mm²125 A97 A14.3 V (2.07%)675.7 V23.58 V (3.42%)2228.7 W✓ OK (≤3%)
50 mm²151 A118 A10.01 V (1.45%)680.0 V16.51 V (2.39%)1560.1 W✓ OK (≤3%)
70 mm²192 A150 A7.15 V (1.04%)682.9 V11.79 V (1.71%)1114.3 W✓ OK (≤3%)
95 mm²232 A181 A5.27 V (0.76%)684.7 V8.69 V (1.26%)821.1 W✓ OK (≤3%)
120 mm²269 A210 A4.17 V (0.6%)685.8 V6.88 V (1.0%)650.0 W✓ OK (≤3%)
150 mm²309 A241 A3.34 V (0.48%)686.7 V5.5 V (0.8%)520.0 W✓ OK (≤3%)
185 mm²353 A275 A2.7 V (0.39%)687.3 V4.46 V (0.65%)421.6 W✓ OK (≤3%)
240 mm²415 A324 A2.08 V (0.3%)687.9 V3.44 V (0.5%)325.0 W✓ OK (≤3%)
300 mm²477 A372 A1.67 V (0.24%)688.3 V2.75 V (0.4%)260.0 W✓ OK (≤3%)
400 mm²570 A445 A1.25 V (0.18%)688.7 V2.06 V (0.3%)195.0 W✓ OK (≤3%)

FAQ — 90 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 90A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 90A over 150m at 690V (voltage drop: 20.02V or 2.9%).

What is the power capacity of 90A at 690V?

At unity power factor, 90A at 690V supports 107.56 kW with a standard 90A circuit breaker.