⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

900 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 1.2V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.94V (16.55%)
Voltage at Load46.8 VLine Loss: 1083.4 W
Max Power & Breaker43.2 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1284.0 V (2675.0%)0.0 V2118.0 V (4412.5%)1155600.0 WDrop High
2.5 mm²24 A18 A770.4 V (1605.0%)0.0 V1270.8 V (2647.5%)693360.0 WDrop High
4 mm²32 A25 A481.5 V (1003.12%)0.0 V794.25 V (1654.69%)433350.0 WDrop High
6 mm²41 A32 A321.0 V (668.75%)0.0 V529.5 V (1103.12%)288900.0 WDrop High
10 mm²57 A44 A192.6 V (401.25%)0.0 V317.7 V (661.88%)173340.0 WDrop High
16 mm²76 A59 A120.37 V (250.78%)0.0 V198.56 V (413.67%)108337.5 WDrop High
25 mm²101 A78 A77.04 V (160.5%)0.0 V127.08 V (264.75%)69336.0 WDrop High
35 mm²125 A97 A55.03 V (114.64%)0.0 V90.77 V (189.11%)49525.7 WDrop High
50 mm²151 A118 A38.52 V (80.25%)9.5 V63.54 V (132.38%)34668.0 WDrop High
70 mm²192 A150 A27.51 V (57.32%)20.5 V45.39 V (94.55%)24762.9 WDrop High
95 mm²232 A181 A20.27 V (42.24%)27.7 V33.44 V (69.67%)18246.3 WDrop High
120 mm²269 A210 A16.05 V (33.44%)32.0 V26.47 V (55.16%)14445.0 WDrop High
150 mm²309 A241 A12.84 V (26.75%)35.2 V21.18 V (44.12%)11556.0 WDrop High
185 mm²353 A275 A10.41 V (21.69%)37.6 V17.17 V (35.78%)9369.7 WDrop High
240 mm²415 A324 A8.02 V (16.72%)40.0 V13.24 V (27.58%)7222.5 WDrop High
300 mm²477 A372 A6.42 V (13.37%)41.6 V10.59 V (22.06%)5778.0 WDrop High
400 mm²570 A445 A4.81 V (10.03%)43.2 V7.94 V (16.55%)4333.5 WDrop High

FAQ — 900 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 900A at 50 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 900A over 50m at 48V (voltage drop: 1.2V or 2.51%).

What is the power capacity of 900A at 48V?

At unity power factor, 900A at 48V supports 43.2 kW with a standard 1000A circuit breaker.