25 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.26V (2.63%)
Voltage at Load46.9 VLine Loss: 26.7 W
Max Power & Breaker1.2 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A35.67 V (74.31%)12.3 V58.83 V (122.57%)891.7 WDrop High
2.5 mm²24 A18 A21.4 V (44.58%)26.6 V35.3 V (73.54%)535.0 WDrop High
4 mm²32 A25 A13.37 V (27.86%)34.6 V22.06 V (45.96%)334.4 WDrop High
6 mm²41 A32 A8.92 V (18.58%)39.1 V14.71 V (30.64%)222.9 WDrop High
10 mm²57 A44 A5.35 V (11.15%)42.6 V8.82 V (18.39%)133.7 WDrop High
16 mm²76 A59 A3.34 V (6.97%)44.7 V5.52 V (11.49%)83.6 WDrop High
25 mm²101 A78 A2.14 V (4.46%)45.9 V3.53 V (7.35%)53.5 W~ ≤5%
35 mm²125 A97 A1.53 V (3.18%)46.5 V2.52 V (5.25%)38.2 W~ ≤5%
50 mm²151 A118 A1.07 V (2.23%)46.9 V1.76 V (3.68%)26.7 W✓ OK (≤3%)
70 mm²192 A150 A0.76 V (1.59%)47.2 V1.26 V (2.63%)19.1 W✓ OK (≤3%)
95 mm²232 A181 A0.56 V (1.17%)47.4 V0.93 V (1.94%)14.1 W✓ OK (≤3%)
120 mm²269 A210 A0.45 V (0.93%)47.6 V0.74 V (1.53%)11.1 W✓ OK (≤3%)
150 mm²309 A241 A0.36 V (0.74%)47.6 V0.59 V (1.23%)8.9 W✓ OK (≤3%)
185 mm²353 A275 A0.29 V (0.6%)47.7 V0.48 V (0.99%)7.2 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.46%)47.8 V0.37 V (0.77%)5.6 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.37%)47.8 V0.29 V (0.61%)4.5 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.28%)47.9 V0.22 V (0.46%)3.3 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 25A at 50 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 25A over 50m at 48V (voltage drop: 1.07V or 2.23%).

What is the power capacity of 25A at 48V?

At unity power factor, 25A at 48V supports 1.2 kW with a standard 25A circuit breaker.