Kabeltværsnit for 1000 Ampere ved 500 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 1000 A over 500 m ved 400V.
Copper Cable (≤3% Drop)4× 400 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 76.43V (19.11%)
Voltage at Load388.4 VLine Loss: 20062.5 W
Max Power & Breaker692.82 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 500m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 12355.3 V (3088.82%) | 0.0 V | 20380.46 V (5095.12%) | 21400000.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 7413.18 V (1853.29%) | 0.0 V | 12228.28 V (3057.07%) | 12840000.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 4633.24 V (1158.31%) | 0.0 V | 7642.67 V (1910.67%) | 8025000.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 3088.82 V (772.21%) | 0.0 V | 5095.12 V (1273.78%) | 5350000.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 1853.29 V (463.32%) | 0.0 V | 3057.07 V (764.27%) | 3210000.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 1158.31 V (289.58%) | 0.0 V | 1910.67 V (477.67%) | 2006250.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 741.32 V (185.33%) | 0.0 V | 1222.83 V (305.71%) | 1284000.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 529.51 V (132.38%) | 0.0 V | 873.45 V (218.36%) | 917142.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 370.66 V (92.66%) | 29.3 V | 611.41 V (152.85%) | 642000.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 264.76 V (66.19%) | 135.2 V | 436.72 V (109.18%) | 458571.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 195.08 V (48.77%) | 204.9 V | 321.8 V (80.45%) | 337894.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 154.44 V (38.61%) | 245.6 V | 254.76 V (63.69%) | 267500.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 123.55 V (30.89%) | 276.4 V | 203.8 V (50.95%) | 214000.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 100.18 V (25.04%) | 299.8 V | 165.25 V (41.31%) | 173513.5 W | Drop High |
| 240 mm² | 415 A | 324 A | 77.22 V (19.31%) | 322.8 V | 127.38 V (31.84%) | 133750.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 61.78 V (15.44%) | 338.2 V | 101.9 V (25.48%) | 107000.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 46.33 V (11.58%) | 353.7 V | 76.43 V (19.11%) | 80250.0 W | Drop High |
FAQ — Kabeltværsnit for 1000 Ampere ved 500 Meter (400V)
Hvilket kabeltværsnit kræves til 1000A ved 500 meter (400V)?
Til 1000 Ampere over 500 meter ved 400V anbefales 4× 400 mm² kobberkabel (spændingsfald 11.58V / 2.9%).
Hvor mange kW svarer 1000A ved 400V til?
Det svarer til 692.82 kW med en anbefalet sikring på 1000A.
Related Lengths & Currents (400V)
1000A · 5m (400V)1000A · 10m (400V)1000A · 15m (400V)1000A · 20m (400V)1000A · 25m (400V)1000A · 30m (400V)1000A · 35m (400V)1000A · 40m (400V)1000A · 45m (400V)1000A · 50m (400V)1000A · 60m (400V)1000A · 70m (400V)10A · 500m (400V)16A · 500m (400V)20A · 500m (400V)25A · 500m (400V)32A · 500m (400V)40A · 500m (400V)50A · 500m (400V)63A · 500m (400V)80A · 500m (400V)100A · 500m (400V)125A · 500m (400V)160A · 500m (400V)200A · 500m (400V)