Kabeltværsnit for 1000 Ampere ved 35 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 1000 A over 35 m ved 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.62V (0.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.35V (1.34%)
Voltage at Load398.4 VLine Loss: 2808.8 W
Max Power & Breaker692.82 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 864.87 V (216.22%) | 0.0 V | 1426.63 V (356.66%) | 1498000.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 518.92 V (129.73%) | 0.0 V | 855.98 V (213.99%) | 898800.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 324.33 V (81.08%) | 75.7 V | 534.99 V (133.75%) | 561750.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 216.22 V (54.05%) | 183.8 V | 356.66 V (89.16%) | 374500.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 129.73 V (32.43%) | 270.3 V | 213.99 V (53.5%) | 224700.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 81.08 V (20.27%) | 318.9 V | 133.75 V (33.44%) | 140437.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 51.89 V (12.97%) | 348.1 V | 85.6 V (21.4%) | 89880.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 37.07 V (9.27%) | 362.9 V | 61.14 V (15.29%) | 64200.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 44940.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 32100.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 13.66 V (3.41%) | 386.3 V | 22.53 V (5.63%) | 23652.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 10.81 V (2.7%) | 389.2 V | 17.83 V (4.46%) | 18725.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 8.65 V (2.16%) | 391.4 V | 14.27 V (3.57%) | 14980.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 7.01 V (1.75%) | 393.0 V | 11.57 V (2.89%) | 12145.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 5.41 V (1.35%) | 394.6 V | 8.92 V (2.23%) | 9362.5 W | Drop High |
| 300 mm² | 477 A | 372 A | 4.32 V (1.08%) | 395.7 V | 7.13 V (1.78%) | 7490.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 3.24 V (0.81%) | 396.8 V | 5.35 V (1.34%) | 5617.5 W | Drop High |
FAQ — Kabeltværsnit for 1000 Ampere ved 35 Meter (400V)
Hvilket kabeltværsnit kræves til 1000A ved 35 meter (400V)?
Til 1000 Ampere over 35 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 1.62V / 0.41%).
Hvor mange kW svarer 1000A ved 400V til?
Det svarer til 692.82 kW med en anbefalet sikring på 1000A.
Related Lengths & Currents (400V)
1000A · 5m (400V)1000A · 10m (400V)1000A · 15m (400V)1000A · 20m (400V)1000A · 25m (400V)1000A · 30m (400V)1000A · 40m (400V)1000A · 45m (400V)1000A · 50m (400V)1000A · 60m (400V)1000A · 70m (400V)10A · 35m (400V)16A · 35m (400V)20A · 35m (400V)25A · 35m (400V)32A · 35m (400V)40A · 35m (400V)50A · 35m (400V)63A · 35m (400V)80A · 35m (400V)100A · 35m (400V)125A · 35m (400V)160A · 35m (400V)200A · 35m (400V)