Kabeltværsnit for 125 Ampere ved 150 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 125 A over 150 m ved 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 9.93V (2.48%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 9.55V (2.39%)
Voltage at Load390.1 VLine Loss: 2149.6 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A463.32 V (115.83%)0.0 V764.27 V (191.07%)100312.5 WDrop High
2.5 mm²24 A18 A277.99 V (69.5%)122.0 V458.56 V (114.64%)60187.5 WDrop High
4 mm²32 A25 A173.75 V (43.44%)226.3 V286.6 V (71.65%)37617.2 WDrop High
6 mm²41 A32 A115.83 V (28.96%)284.2 V191.07 V (47.77%)25078.1 WDrop High
10 mm²57 A44 A69.5 V (17.37%)330.5 V114.64 V (28.66%)15046.9 WDrop High
16 mm²76 A59 A43.44 V (10.86%)356.6 V71.65 V (17.91%)9404.3 WDrop High
25 mm²101 A78 A27.8 V (6.95%)372.2 V45.86 V (11.46%)6018.7 WDrop High
35 mm²125 A97 A19.86 V (4.96%)380.1 V32.75 V (8.19%)4299.1 W~ ≤5%
50 mm²151 A118 A13.9 V (3.47%)386.1 V22.93 V (5.73%)3009.4 W~ ≤5%
70 mm²192 A150 A9.93 V (2.48%)390.1 V16.38 V (4.09%)2149.6 W✓ OK (≤3%)
95 mm²232 A181 A7.32 V (1.83%)392.7 V12.07 V (3.02%)1583.9 W✓ OK (≤3%)
120 mm²269 A210 A5.79 V (1.45%)394.2 V9.55 V (2.39%)1253.9 W✓ OK (≤3%)
150 mm²309 A241 A4.63 V (1.16%)395.4 V7.64 V (1.91%)1003.1 W✓ OK (≤3%)
185 mm²353 A275 A3.76 V (0.94%)396.2 V6.2 V (1.55%)813.3 W✓ OK (≤3%)
240 mm²415 A324 A2.9 V (0.72%)397.1 V4.78 V (1.19%)627.0 W✓ OK (≤3%)
300 mm²477 A372 A2.32 V (0.58%)397.7 V3.82 V (0.96%)501.6 W✓ OK (≤3%)
400 mm²570 A445 A1.74 V (0.43%)398.3 V2.87 V (0.72%)376.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 125 Ampere ved 150 Meter (400V)

Hvilket kabeltværsnit kræves til 125A ved 150 meter (400V)?

Til 125 Ampere over 150 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 9.93V / 2.48%).

Hvor mange kW svarer 125A ved 400V til?

Det svarer til 86.6 kW med en anbefalet sikring på 125A.