Kabeltværsnit for 125 Ampere ved 25 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 125 A over 25 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 3.31V (0.83%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 2.73V (0.68%)
Voltage at Load396.7 VLine Loss: 716.5 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A77.22 V (19.31%)322.8 V127.38 V (31.84%)16718.8 WDrop High
2.5 mm²24 A18 A46.33 V (11.58%)353.7 V76.43 V (19.11%)10031.2 WDrop High
4 mm²32 A25 A28.96 V (7.24%)371.0 V47.77 V (11.94%)6269.5 WDrop High
6 mm²41 A32 A19.31 V (4.83%)380.7 V31.84 V (7.96%)4179.7 WDrop High
10 mm²57 A44 A11.58 V (2.9%)388.4 V19.11 V (4.78%)2507.8 WDrop High
16 mm²76 A59 A7.24 V (1.81%)392.8 V11.94 V (2.99%)1567.4 WDrop High
25 mm²101 A78 A4.63 V (1.16%)395.4 V7.64 V (1.91%)1003.1 WDrop High
35 mm²125 A97 A3.31 V (0.83%)396.7 V5.46 V (1.36%)716.5 W✓ OK (≤3%)
50 mm²151 A118 A2.32 V (0.58%)397.7 V3.82 V (0.96%)501.6 W✓ OK (≤3%)
70 mm²192 A150 A1.65 V (0.41%)398.3 V2.73 V (0.68%)358.3 W✓ OK (≤3%)
95 mm²232 A181 A1.22 V (0.3%)398.8 V2.01 V (0.5%)264.0 W✓ OK (≤3%)
120 mm²269 A210 A0.97 V (0.24%)399.0 V1.59 V (0.4%)209.0 W✓ OK (≤3%)
150 mm²309 A241 A0.77 V (0.19%)399.2 V1.27 V (0.32%)167.2 W✓ OK (≤3%)
185 mm²353 A275 A0.63 V (0.16%)399.4 V1.03 V (0.26%)135.6 W✓ OK (≤3%)
240 mm²415 A324 A0.48 V (0.12%)399.5 V0.8 V (0.2%)104.5 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.1%)399.6 V0.64 V (0.16%)83.6 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.07%)399.7 V0.48 V (0.12%)62.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 125 Ampere ved 25 Meter (400V)

Hvilket kabeltværsnit kræves til 125A ved 25 meter (400V)?

Til 125 Ampere over 25 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 3.31V / 0.83%).

Hvor mange kW svarer 125A ved 400V til?

Det svarer til 86.6 kW med en anbefalet sikring på 125A.