Kabeltværsnit for 125 Ampere ved 300 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 125 A over 300 m ved 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.62V (2.88%)
Voltage at Load223.3 VLine Loss: 835.9 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1070.0 V (465.22%)0.0 V1765.0 V (767.39%)133750.0 WDrop High
2.5 mm²24 A18 A642.0 V (279.13%)0.0 V1059.0 V (460.43%)80250.0 WDrop High
4 mm²32 A25 A401.25 V (174.46%)0.0 V661.88 V (287.77%)50156.2 WDrop High
6 mm²41 A32 A267.5 V (116.3%)0.0 V441.25 V (191.85%)33437.5 WDrop High
10 mm²57 A44 A160.5 V (69.78%)69.5 V264.75 V (115.11%)20062.5 WDrop High
16 mm²76 A59 A100.31 V (43.61%)129.7 V165.47 V (71.94%)12539.1 WDrop High
25 mm²101 A78 A64.2 V (27.91%)165.8 V105.9 V (46.04%)8025.0 WDrop High
35 mm²125 A97 A45.86 V (19.94%)184.1 V75.64 V (32.89%)5732.1 WDrop High
50 mm²151 A118 A32.1 V (13.96%)197.9 V52.95 V (23.02%)4012.5 WDrop High
70 mm²192 A150 A22.93 V (9.97%)207.1 V37.82 V (16.44%)2866.1 WDrop High
95 mm²232 A181 A16.89 V (7.35%)213.1 V27.87 V (12.12%)2111.8 WDrop High
120 mm²269 A210 A13.38 V (5.82%)216.6 V22.06 V (9.59%)1671.9 WDrop High
150 mm²309 A241 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1337.5 W~ ≤5%
185 mm²353 A275 A8.68 V (3.77%)221.3 V14.31 V (6.22%)1084.5 W~ ≤5%
240 mm²415 A324 A6.69 V (2.91%)223.3 V11.03 V (4.8%)835.9 W✓ OK (≤3%)
300 mm²477 A372 A5.35 V (2.33%)224.7 V8.82 V (3.84%)668.8 W✓ OK (≤3%)
400 mm²570 A445 A4.01 V (1.74%)226.0 V6.62 V (2.88%)501.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 125 Ampere ved 300 Meter (230V)

Hvilket kabeltværsnit kræves til 125A ved 300 meter (230V)?

Til 125 Ampere over 300 meter ved 230V anbefales 240 mm² kobberkabel (spændingsfald 6.69V / 2.91%).

Hvor mange kW svarer 125A ved 230V til?

Det svarer til 28.75 kW med en anbefalet sikring på 125A.