Kabeltværsnit for 125 Ampere ved 10 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 125 A over 10 m ved 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 1.53V (0.66%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.26V (0.55%)
Voltage at Load228.5 VLine Loss: 191.1 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A35.67 V (15.51%)194.3 V58.83 V (25.58%)4458.3 WDrop High
2.5 mm²24 A18 A21.4 V (9.3%)208.6 V35.3 V (15.35%)2675.0 WDrop High
4 mm²32 A25 A13.38 V (5.82%)216.6 V22.06 V (9.59%)1671.9 WDrop High
6 mm²41 A32 A8.92 V (3.88%)221.1 V14.71 V (6.39%)1114.6 WDrop High
10 mm²57 A44 A5.35 V (2.33%)224.7 V8.82 V (3.84%)668.8 WDrop High
16 mm²76 A59 A3.34 V (1.45%)226.7 V5.52 V (2.4%)418.0 WDrop High
25 mm²101 A78 A2.14 V (0.93%)227.9 V3.53 V (1.53%)267.5 WDrop High
35 mm²125 A97 A1.53 V (0.66%)228.5 V2.52 V (1.1%)191.1 W✓ OK (≤3%)
50 mm²151 A118 A1.07 V (0.47%)228.9 V1.76 V (0.77%)133.8 W✓ OK (≤3%)
70 mm²192 A150 A0.76 V (0.33%)229.2 V1.26 V (0.55%)95.5 W✓ OK (≤3%)
95 mm²232 A181 A0.56 V (0.24%)229.4 V0.93 V (0.4%)70.4 W✓ OK (≤3%)
120 mm²269 A210 A0.45 V (0.19%)229.6 V0.74 V (0.32%)55.7 W✓ OK (≤3%)
150 mm²309 A241 A0.36 V (0.16%)229.6 V0.59 V (0.26%)44.6 W✓ OK (≤3%)
185 mm²353 A275 A0.29 V (0.13%)229.7 V0.48 V (0.21%)36.1 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.1%)229.8 V0.37 V (0.16%)27.9 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.08%)229.8 V0.29 V (0.13%)22.3 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.06%)229.9 V0.22 V (0.1%)16.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 125 Ampere ved 10 Meter (230V)

Hvilket kabeltværsnit kræves til 125A ved 10 meter (230V)?

Til 125 Ampere over 10 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 1.53V / 0.66%).

Hvor mange kW svarer 125A ved 230V til?

Det svarer til 28.75 kW med en anbefalet sikring på 125A.