⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 150 Ampere ved 10 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 150 A over 10 m ved 400V.

Copper Cable (≤3% Drop)50 mm²Drop: 1.11V (0.28%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.31V (0.33%)
Voltage at Load398.9 VLine Loss: 288.9 W
Max Power & Breaker103.92 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (9.27%)362.9 V61.14 V (15.29%)9630.0 WDrop High
2.5 mm²24 A18 A22.24 V (5.56%)377.8 V36.68 V (9.17%)5778.0 WDrop High
4 mm²32 A25 A13.9 V (3.47%)386.1 V22.93 V (5.73%)3611.2 WDrop High
6 mm²41 A32 A9.27 V (2.32%)390.7 V15.29 V (3.82%)2407.5 WDrop High
10 mm²57 A44 A5.56 V (1.39%)394.4 V9.17 V (2.29%)1444.5 WDrop High
16 mm²76 A59 A3.47 V (0.87%)396.5 V5.73 V (1.43%)902.8 WDrop High
25 mm²101 A78 A2.22 V (0.56%)397.8 V3.67 V (0.92%)577.8 WDrop High
35 mm²125 A97 A1.59 V (0.4%)398.4 V2.62 V (0.66%)412.7 WDrop High
50 mm²151 A118 A1.11 V (0.28%)398.9 V1.83 V (0.46%)288.9 W✓ OK (≤3%)
70 mm²192 A150 A0.79 V (0.2%)399.2 V1.31 V (0.33%)206.4 W✓ OK (≤3%)
95 mm²232 A181 A0.59 V (0.15%)399.4 V0.97 V (0.24%)152.1 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.12%)399.5 V0.76 V (0.19%)120.4 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.09%)399.6 V0.61 V (0.15%)96.3 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.08%)399.7 V0.5 V (0.12%)78.1 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.06%)399.8 V0.38 V (0.1%)60.2 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.31 V (0.08%)48.1 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.03%)399.9 V0.23 V (0.06%)36.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 150 Ampere ved 10 Meter (400V)

Hvilket kabeltværsnit kræves til 150A ved 10 meter (400V)?

Til 150 Ampere over 10 meter ved 400V anbefales 50 mm² kobberkabel (spændingsfald 1.11V / 0.28%).

Hvor mange kW svarer 150A ved 400V til?

Det svarer til 103.92 kW med en anbefalet sikring på 150A.