Kabeltværsnit for 40 Ampere ved 10 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 40 A over 10 m ved 400V.
Copper Cable (≤3% Drop)6 mm²Drop: 2.47V (0.62%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 2.45V (0.61%)
Voltage at Load397.5 VLine Loss: 171.2 W
Max Power & Breaker27.71 kW40A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 9.88 V (2.47%) | 390.1 V | 16.3 V (4.08%) | 684.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 5.93 V (1.48%) | 394.1 V | 9.78 V (2.45%) | 410.9 W | Drop High |
| 4 mm² | 32 A | 25 A | 3.71 V (0.93%) | 396.3 V | 6.11 V (1.53%) | 256.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 2.47 V (0.62%) | 397.5 V | 4.08 V (1.02%) | 171.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.48 V (0.37%) | 398.5 V | 2.45 V (0.61%) | 102.7 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.93 V (0.23%) | 399.1 V | 1.53 V (0.38%) | 64.2 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.59 V (0.15%) | 399.4 V | 0.98 V (0.24%) | 41.1 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.42 V (0.11%) | 399.6 V | 0.7 V (0.17%) | 29.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.3 V (0.07%) | 399.7 V | 0.49 V (0.12%) | 20.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.21 V (0.05%) | 399.8 V | 0.35 V (0.09%) | 14.7 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.16 V (0.04%) | 399.8 V | 0.26 V (0.06%) | 10.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 8.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.1 V (0.02%) | 399.9 V | 0.16 V (0.04%) | 6.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.08 V (0.02%) | 399.9 V | 0.13 V (0.03%) | 5.6 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.06 V (0.02%) | 399.9 V | 0.1 V (0.03%) | 4.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.05 V (0.01%) | 400.0 V | 0.08 V (0.02%) | 3.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.04 V (0.01%) | 400.0 V | 0.06 V (0.02%) | 2.6 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 40 Ampere ved 10 Meter (400V)
Hvilket kabeltværsnit kræves til 40A ved 10 meter (400V)?
Til 40 Ampere over 10 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 2.47V / 0.62%).
Hvor mange kW svarer 40A ved 400V til?
Det svarer til 27.71 kW med en anbefalet sikring på 40A.
Related Lengths & Currents (400V)
40A · 5m (400V)40A · 15m (400V)40A · 20m (400V)40A · 25m (400V)40A · 30m (400V)40A · 35m (400V)40A · 40m (400V)40A · 45m (400V)40A · 50m (400V)40A · 60m (400V)40A · 70m (400V)10A · 10m (400V)16A · 10m (400V)20A · 10m (400V)25A · 10m (400V)32A · 10m (400V)50A · 10m (400V)63A · 10m (400V)80A · 10m (400V)100A · 10m (400V)125A · 10m (400V)160A · 10m (400V)200A · 10m (400V)