Kabeltværsnit for 150 Ampere ved 35 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 150 A over 35 m ved 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 4.49V (1.95%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.29V (2.3%)
Voltage at Load225.5 VLine Loss: 674.1 W
Max Power & Breaker34.5 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A149.8 V (65.13%)80.2 V247.1 V (107.43%)22470.0 WDrop High
2.5 mm²24 A18 A89.88 V (39.08%)140.1 V148.26 V (64.46%)13482.0 WDrop High
4 mm²32 A25 A56.17 V (24.42%)173.8 V92.66 V (40.29%)8426.2 WDrop High
6 mm²41 A32 A37.45 V (16.28%)192.6 V61.77 V (26.86%)5617.5 WDrop High
10 mm²57 A44 A22.47 V (9.77%)207.5 V37.07 V (16.12%)3370.5 WDrop High
16 mm²76 A59 A14.04 V (6.11%)216.0 V23.17 V (10.07%)2106.6 WDrop High
25 mm²101 A78 A8.99 V (3.91%)221.0 V14.83 V (6.45%)1348.2 WDrop High
35 mm²125 A97 A6.42 V (2.79%)223.6 V10.59 V (4.6%)963.0 WDrop High
50 mm²151 A118 A4.49 V (1.95%)225.5 V7.41 V (3.22%)674.1 W✓ OK (≤3%)
70 mm²192 A150 A3.21 V (1.4%)226.8 V5.29 V (2.3%)481.5 W✓ OK (≤3%)
95 mm²232 A181 A2.37 V (1.03%)227.6 V3.9 V (1.7%)354.8 W✓ OK (≤3%)
120 mm²269 A210 A1.87 V (0.81%)228.1 V3.09 V (1.34%)280.9 W✓ OK (≤3%)
150 mm²309 A241 A1.5 V (0.65%)228.5 V2.47 V (1.07%)224.7 W✓ OK (≤3%)
185 mm²353 A275 A1.21 V (0.53%)228.8 V2.0 V (0.87%)182.2 W✓ OK (≤3%)
240 mm²415 A324 A0.94 V (0.41%)229.1 V1.54 V (0.67%)140.4 W✓ OK (≤3%)
300 mm²477 A372 A0.75 V (0.33%)229.3 V1.24 V (0.54%)112.3 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (0.24%)229.4 V0.93 V (0.4%)84.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 150 Ampere ved 35 Meter (230V)

Hvilket kabeltværsnit kræves til 150A ved 35 meter (230V)?

Til 150 Ampere over 35 meter ved 230V anbefales 50 mm² kobberkabel (spændingsfald 4.49V / 1.95%).

Hvor mange kW svarer 150A ved 230V til?

Det svarer til 34.5 kW med en anbefalet sikring på 150A.