Kabeltværsnit for 150 Ampere ved 10 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 150 A over 10 m ved 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 1.28V (0.56%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.51V (0.66%)
Voltage at Load228.7 VLine Loss: 192.6 W
Max Power & Breaker34.5 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A42.8 V (18.61%)187.2 V70.6 V (30.7%)6420.0 WDrop High
2.5 mm²24 A18 A25.68 V (11.17%)204.3 V42.36 V (18.42%)3852.0 WDrop High
4 mm²32 A25 A16.05 V (6.98%)213.9 V26.47 V (11.51%)2407.5 WDrop High
6 mm²41 A32 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1605.0 WDrop High
10 mm²57 A44 A6.42 V (2.79%)223.6 V10.59 V (4.6%)963.0 WDrop High
16 mm²76 A59 A4.01 V (1.74%)226.0 V6.62 V (2.88%)601.9 WDrop High
25 mm²101 A78 A2.57 V (1.12%)227.4 V4.24 V (1.84%)385.2 WDrop High
35 mm²125 A97 A1.83 V (0.8%)228.2 V3.03 V (1.32%)275.1 WDrop High
50 mm²151 A118 A1.28 V (0.56%)228.7 V2.12 V (0.92%)192.6 W✓ OK (≤3%)
70 mm²192 A150 A0.92 V (0.4%)229.1 V1.51 V (0.66%)137.6 W✓ OK (≤3%)
95 mm²232 A181 A0.68 V (0.29%)229.3 V1.11 V (0.48%)101.4 W✓ OK (≤3%)
120 mm²269 A210 A0.54 V (0.23%)229.5 V0.88 V (0.38%)80.2 W✓ OK (≤3%)
150 mm²309 A241 A0.43 V (0.19%)229.6 V0.71 V (0.31%)64.2 W✓ OK (≤3%)
185 mm²353 A275 A0.35 V (0.15%)229.7 V0.57 V (0.25%)52.1 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (0.12%)229.7 V0.44 V (0.19%)40.1 W✓ OK (≤3%)
300 mm²477 A372 A0.21 V (0.09%)229.8 V0.35 V (0.15%)32.1 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.07%)229.8 V0.26 V (0.12%)24.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 150 Ampere ved 10 Meter (230V)

Hvilket kabeltværsnit kræves til 150A ved 10 meter (230V)?

Til 150 Ampere over 10 meter ved 230V anbefales 50 mm² kobberkabel (spændingsfald 1.28V / 0.56%).

Hvor mange kW svarer 150A ved 230V til?

Det svarer til 34.5 kW med en anbefalet sikring på 150A.