Kabeltværsnit for 20 Ampere ved 5 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 20 A over 5 m ved 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 1.48V (0.37%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 1.53V (0.38%)
Voltage at Load398.5 VLine Loss: 51.4 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2.47 V (0.62%)397.5 V4.08 V (1.02%)85.6 WDrop High
2.5 mm²24 A18 A1.48 V (0.37%)398.5 V2.45 V (0.61%)51.4 W✓ OK (≤3%)
4 mm²32 A25 A0.93 V (0.23%)399.1 V1.53 V (0.38%)32.1 W✓ OK (≤3%)
6 mm²41 A32 A0.62 V (0.15%)399.4 V1.02 V (0.25%)21.4 W✓ OK (≤3%)
10 mm²57 A44 A0.37 V (0.09%)399.6 V0.61 V (0.15%)12.8 W✓ OK (≤3%)
16 mm²76 A59 A0.23 V (0.06%)399.8 V0.38 V (0.1%)8.0 W✓ OK (≤3%)
25 mm²101 A78 A0.15 V (0.04%)399.9 V0.24 V (0.06%)5.1 W✓ OK (≤3%)
35 mm²125 A97 A0.11 V (0.03%)399.9 V0.17 V (0.04%)3.7 W✓ OK (≤3%)
50 mm²151 A118 A0.07 V (0.02%)399.9 V0.12 V (0.03%)2.6 W✓ OK (≤3%)
70 mm²192 A150 A0.05 V (0.01%)399.9 V0.09 V (0.02%)1.8 W✓ OK (≤3%)
95 mm²232 A181 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.4 W✓ OK (≤3%)
120 mm²269 A210 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.1 W✓ OK (≤3%)
150 mm²309 A241 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.9 W✓ OK (≤3%)
185 mm²353 A275 A0.02 V (0.01%)400.0 V0.03 V (0.01%)0.7 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.5 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.0%)400.0 V0.02 V (0.01%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.0%)0.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 20 Ampere ved 5 Meter (400V)

Hvilket kabeltværsnit kræves til 20A ved 5 meter (400V)?

Til 20 Ampere over 5 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 1.48V / 0.37%).

Hvor mange kW svarer 20A ved 400V til?

Det svarer til 13.86 kW med en anbefalet sikring på 20A.