Kabeltværsnit for 20 Ampere ved 70 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 20 A over 70 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 8.65V (2.16%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 8.56V (2.14%)
Voltage at Load391.4 VLine Loss: 299.6 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.59 V (8.65%)365.4 V57.07 V (14.27%)1198.4 WDrop High
2.5 mm²24 A18 A20.76 V (5.19%)379.2 V34.24 V (8.56%)719.0 WDrop High
4 mm²32 A25 A12.97 V (3.24%)387.0 V21.4 V (5.35%)449.4 W~ ≤5%
6 mm²41 A32 A8.65 V (2.16%)391.4 V14.27 V (3.57%)299.6 W✓ OK (≤3%)
10 mm²57 A44 A5.19 V (1.3%)394.8 V8.56 V (2.14%)179.8 W✓ OK (≤3%)
16 mm²76 A59 A3.24 V (0.81%)396.8 V5.35 V (1.34%)112.3 W✓ OK (≤3%)
25 mm²101 A78 A2.08 V (0.52%)397.9 V3.42 V (0.86%)71.9 W✓ OK (≤3%)
35 mm²125 A97 A1.48 V (0.37%)398.5 V2.45 V (0.61%)51.4 W✓ OK (≤3%)
50 mm²151 A118 A1.04 V (0.26%)399.0 V1.71 V (0.43%)36.0 W✓ OK (≤3%)
70 mm²192 A150 A0.74 V (0.19%)399.3 V1.22 V (0.31%)25.7 W✓ OK (≤3%)
95 mm²232 A181 A0.55 V (0.14%)399.5 V0.9 V (0.23%)18.9 W✓ OK (≤3%)
120 mm²269 A210 A0.43 V (0.11%)399.6 V0.71 V (0.18%)15.0 W✓ OK (≤3%)
150 mm²309 A241 A0.35 V (0.09%)399.7 V0.57 V (0.14%)12.0 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.07%)399.7 V0.46 V (0.12%)9.7 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.05%)399.8 V0.36 V (0.09%)7.5 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.04%)399.8 V0.29 V (0.07%)6.0 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)399.9 V0.21 V (0.05%)4.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 20 Ampere ved 70 Meter (400V)

Hvilket kabeltværsnit kræves til 20A ved 70 meter (400V)?

Til 20 Ampere over 70 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 8.65V / 2.16%).

Hvor mange kW svarer 20A ved 400V til?

Det svarer til 13.86 kW med en anbefalet sikring på 20A.