Kabeltværsnit for 200 Ampere ved 175 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 200 A over 175 m ved 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 11.57V (2.89%)
Voltage at Load389.2 VLine Loss: 3745.0 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A864.87 V (216.22%)0.0 V1426.63 V (356.66%)299600.0 WDrop High
2.5 mm²24 A18 A518.92 V (129.73%)0.0 V855.98 V (213.99%)179760.0 WDrop High
4 mm²32 A25 A324.33 V (81.08%)75.7 V534.99 V (133.75%)112350.0 WDrop High
6 mm²41 A32 A216.22 V (54.05%)183.8 V356.66 V (89.16%)74900.0 WDrop High
10 mm²57 A44 A129.73 V (32.43%)270.3 V213.99 V (53.5%)44940.0 WDrop High
16 mm²76 A59 A81.08 V (20.27%)318.9 V133.75 V (33.44%)28087.5 WDrop High
25 mm²101 A78 A51.89 V (12.97%)348.1 V85.6 V (21.4%)17976.0 WDrop High
35 mm²125 A97 A37.07 V (9.27%)362.9 V61.14 V (15.29%)12840.0 WDrop High
50 mm²151 A118 A25.95 V (6.49%)374.1 V42.8 V (10.7%)8988.0 WDrop High
70 mm²192 A150 A18.53 V (4.63%)381.5 V30.57 V (7.64%)6420.0 WDrop High
95 mm²232 A181 A13.66 V (3.41%)386.3 V22.53 V (5.63%)4730.5 W~ ≤5%
120 mm²269 A210 A10.81 V (2.7%)389.2 V17.83 V (4.46%)3745.0 W✓ OK (≤3%)
150 mm²309 A241 A8.65 V (2.16%)391.4 V14.27 V (3.57%)2996.0 W✓ OK (≤3%)
185 mm²353 A275 A7.01 V (1.75%)393.0 V11.57 V (2.89%)2429.2 W✓ OK (≤3%)
240 mm²415 A324 A5.41 V (1.35%)394.6 V8.92 V (2.23%)1872.5 W✓ OK (≤3%)
300 mm²477 A372 A4.32 V (1.08%)395.7 V7.13 V (1.78%)1498.0 W✓ OK (≤3%)
400 mm²570 A445 A3.24 V (0.81%)396.8 V5.35 V (1.34%)1123.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 200 Ampere ved 175 Meter (400V)

Hvilket kabeltværsnit kræves til 200A ved 175 meter (400V)?

Til 200 Ampere over 175 meter ved 400V anbefales 120 mm² kobberkabel (spændingsfald 10.81V / 2.7%).

Hvor mange kW svarer 200A ved 400V til?

Det svarer til 138.56 kW med en anbefalet sikring på 200A.