Kabeltværsnit for 63 Ampere ved 175 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 63 A over 175 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 11.68V (2.92%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 9.63V (2.41%)
Voltage at Load388.3 VLine Loss: 1274.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A272.43 V (68.11%)127.6 V449.39 V (112.35%)29727.8 WDrop High
2.5 mm²24 A18 A163.46 V (40.87%)236.5 V269.63 V (67.41%)17836.7 WDrop High
4 mm²32 A25 A102.16 V (25.54%)297.8 V168.52 V (42.13%)11147.9 WDrop High
6 mm²41 A32 A68.11 V (17.03%)331.9 V112.35 V (28.09%)7432.0 WDrop High
10 mm²57 A44 A40.87 V (10.22%)359.1 V67.41 V (16.85%)4459.2 WDrop High
16 mm²76 A59 A25.54 V (6.39%)374.5 V42.13 V (10.53%)2787.0 WDrop High
25 mm²101 A78 A16.35 V (4.09%)383.7 V26.96 V (6.74%)1783.7 W~ ≤5%
35 mm²125 A97 A11.68 V (2.92%)388.3 V19.26 V (4.81%)1274.0 W✓ OK (≤3%)
50 mm²151 A118 A8.17 V (2.04%)391.8 V13.48 V (3.37%)891.8 W✓ OK (≤3%)
70 mm²192 A150 A5.84 V (1.46%)394.2 V9.63 V (2.41%)637.0 W✓ OK (≤3%)
95 mm²232 A181 A4.3 V (1.08%)395.7 V7.1 V (1.77%)469.4 W✓ OK (≤3%)
120 mm²269 A210 A3.41 V (0.85%)396.6 V5.62 V (1.4%)371.6 W✓ OK (≤3%)
150 mm²309 A241 A2.72 V (0.68%)397.3 V4.49 V (1.12%)297.3 W✓ OK (≤3%)
185 mm²353 A275 A2.21 V (0.55%)397.8 V3.64 V (0.91%)241.0 W✓ OK (≤3%)
240 mm²415 A324 A1.7 V (0.43%)398.3 V2.81 V (0.7%)185.8 W✓ OK (≤3%)
300 mm²477 A372 A1.36 V (0.34%)398.6 V2.25 V (0.56%)148.6 W✓ OK (≤3%)
400 mm²570 A445 A1.02 V (0.26%)399.0 V1.69 V (0.42%)111.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 63 Ampere ved 175 Meter (400V)

Hvilket kabeltværsnit kræves til 63A ved 175 meter (400V)?

Til 63 Ampere over 175 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 11.68V / 2.92%).

Hvor mange kW svarer 63A ved 400V til?

Det svarer til 43.65 kW med en anbefalet sikring på 63A.