Kabeltværsnit for 225 Ampere ved 300 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 225 A over 300 m ved 400V.
Copper Cable (≤3% Drop)240 mm²Drop: 10.42V (2.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.32V (2.58%)
Voltage at Load389.6 VLine Loss: 4062.7 W
Max Power & Breaker155.88 kW225A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 300m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1667.96 V (416.99%) | 0.0 V | 2751.36 V (687.84%) | 650025.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1000.78 V (250.19%) | 0.0 V | 1650.82 V (412.7%) | 390015.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 625.49 V (156.37%) | 0.0 V | 1031.76 V (257.94%) | 243759.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 416.99 V (104.25%) | 0.0 V | 687.84 V (171.96%) | 162506.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 250.19 V (62.55%) | 149.8 V | 412.7 V (103.18%) | 97503.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 156.37 V (39.09%) | 243.6 V | 257.94 V (64.49%) | 60939.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 100.08 V (25.02%) | 299.9 V | 165.08 V (41.27%) | 39001.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 71.48 V (17.87%) | 328.5 V | 117.92 V (29.48%) | 27858.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 50.04 V (12.51%) | 350.0 V | 82.54 V (20.64%) | 19500.7 W | Drop High |
| 70 mm² | 192 A | 150 A | 35.74 V (8.94%) | 364.3 V | 58.96 V (14.74%) | 13929.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 26.34 V (6.58%) | 373.7 V | 43.44 V (10.86%) | 10263.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 20.85 V (5.21%) | 379.2 V | 34.39 V (8.6%) | 8125.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 16.68 V (4.17%) | 383.3 V | 27.51 V (6.88%) | 6500.2 W | ~ ≤5% |
| 185 mm² | 353 A | 275 A | 13.52 V (3.38%) | 386.5 V | 22.31 V (5.58%) | 5270.5 W | ~ ≤5% |
| 240 mm² | 415 A | 324 A | 10.42 V (2.61%) | 389.6 V | 17.2 V (4.3%) | 4062.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 8.34 V (2.08%) | 391.7 V | 13.76 V (3.44%) | 3250.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 6.25 V (1.56%) | 393.7 V | 10.32 V (2.58%) | 2437.6 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 225 Ampere ved 300 Meter (400V)
Hvilket kabeltværsnit kræves til 225A ved 300 meter (400V)?
Til 225 Ampere over 300 meter ved 400V anbefales 240 mm² kobberkabel (spændingsfald 10.42V / 2.61%).
Hvor mange kW svarer 225A ved 400V til?
Det svarer til 155.88 kW med en anbefalet sikring på 225A.
Related Lengths & Currents (400V)
225A · 5m (400V)225A · 10m (400V)225A · 15m (400V)225A · 20m (400V)225A · 25m (400V)225A · 30m (400V)225A · 35m (400V)225A · 40m (400V)225A · 45m (400V)225A · 50m (400V)225A · 60m (400V)225A · 70m (400V)10A · 300m (400V)16A · 300m (400V)20A · 300m (400V)25A · 300m (400V)32A · 300m (400V)40A · 300m (400V)50A · 300m (400V)63A · 300m (400V)80A · 300m (400V)100A · 300m (400V)125A · 300m (400V)160A · 300m (400V)200A · 300m (400V)