Kabeltværsnit for 225 Ampere ved 60 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 225 A over 60 m ved 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.27V (1.32%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 5.5V (1.38%)
Voltage at Load394.7 VLine Loss: 2052.7 W
Max Power & Breaker155.88 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A333.59 V (83.4%)66.4 V550.27 V (137.57%)130005.0 WDrop High
2.5 mm²24 A18 A200.16 V (50.04%)199.8 V330.16 V (82.54%)78003.0 WDrop High
4 mm²32 A25 A125.1 V (31.27%)274.9 V206.35 V (51.59%)48751.9 WDrop High
6 mm²41 A32 A83.4 V (20.85%)316.6 V137.57 V (34.39%)32501.2 WDrop High
10 mm²57 A44 A50.04 V (12.51%)350.0 V82.54 V (20.64%)19500.8 WDrop High
16 mm²76 A59 A31.27 V (7.82%)368.7 V51.59 V (12.9%)12188.0 WDrop High
25 mm²101 A78 A20.02 V (5.0%)380.0 V33.02 V (8.25%)7800.3 WDrop High
35 mm²125 A97 A14.3 V (3.57%)385.7 V23.58 V (5.9%)5571.6 WDrop High
50 mm²151 A118 A10.01 V (2.5%)390.0 V16.51 V (4.13%)3900.2 WDrop High
70 mm²192 A150 A7.15 V (1.79%)392.9 V11.79 V (2.95%)2785.8 WDrop High
95 mm²232 A181 A5.27 V (1.32%)394.7 V8.69 V (2.17%)2052.7 W✓ OK (≤3%)
120 mm²269 A210 A4.17 V (1.04%)395.8 V6.88 V (1.72%)1625.1 W✓ OK (≤3%)
150 mm²309 A241 A3.34 V (0.83%)396.7 V5.5 V (1.38%)1300.0 W✓ OK (≤3%)
185 mm²353 A275 A2.7 V (0.68%)397.3 V4.46 V (1.12%)1054.1 W✓ OK (≤3%)
240 mm²415 A324 A2.08 V (0.52%)397.9 V3.44 V (0.86%)812.5 W✓ OK (≤3%)
300 mm²477 A372 A1.67 V (0.42%)398.3 V2.75 V (0.69%)650.0 W✓ OK (≤3%)
400 mm²570 A445 A1.25 V (0.31%)398.7 V2.06 V (0.52%)487.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 225 Ampere ved 60 Meter (400V)

Hvilket kabeltværsnit kræves til 225A ved 60 meter (400V)?

Til 225 Ampere over 60 meter ved 400V anbefales 95 mm² kobberkabel (spændingsfald 5.27V / 1.32%).

Hvor mange kW svarer 225A ved 400V til?

Det svarer til 155.88 kW med en anbefalet sikring på 225A.