Kabeltværsnit for 25 Ampere ved 25 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 25 A over 25 m ved 230V.
Copper Cable (≤3% Drop)4 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 4.41V (1.92%)
Voltage at Load223.3 VLine Loss: 167.2 W
Max Power & Breaker5.75 kW25A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 17.83 V (7.75%) | 212.2 V | 29.42 V (12.79%) | 445.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 10.7 V (4.65%) | 219.3 V | 17.65 V (7.67%) | 267.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 6.69 V (2.91%) | 223.3 V | 11.03 V (4.8%) | 167.2 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 4.46 V (1.94%) | 225.5 V | 7.35 V (3.2%) | 111.5 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.67 V (1.16%) | 227.3 V | 4.41 V (1.92%) | 66.9 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.67 V (0.73%) | 228.3 V | 2.76 V (1.2%) | 41.8 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.07 V (0.47%) | 228.9 V | 1.76 V (0.77%) | 26.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.76 V (0.33%) | 229.2 V | 1.26 V (0.55%) | 19.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.53 V (0.23%) | 229.5 V | 0.88 V (0.38%) | 13.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.38 V (0.17%) | 229.6 V | 0.63 V (0.27%) | 9.6 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.28 V (0.12%) | 229.7 V | 0.46 V (0.2%) | 7.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.22 V (0.1%) | 229.8 V | 0.37 V (0.16%) | 5.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.18 V (0.08%) | 229.8 V | 0.29 V (0.13%) | 4.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.14 V (0.06%) | 229.9 V | 0.24 V (0.1%) | 3.6 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.11 V (0.05%) | 229.9 V | 0.18 V (0.08%) | 2.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.09 V (0.04%) | 229.9 V | 0.15 V (0.06%) | 2.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.07 V (0.03%) | 229.9 V | 0.11 V (0.05%) | 1.7 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 25 Ampere ved 25 Meter (230V)
Hvilket kabeltværsnit kræves til 25A ved 25 meter (230V)?
Til 25 Ampere over 25 meter ved 230V anbefales 4 mm² kobberkabel (spændingsfald 6.69V / 2.91%).
Hvor mange kW svarer 25A ved 230V til?
Det svarer til 5.75 kW med en anbefalet sikring på 25A.
Related Lengths & Currents (230V)
25A · 5m (230V)25A · 10m (230V)25A · 15m (230V)25A · 20m (230V)25A · 30m (230V)25A · 35m (230V)25A · 40m (230V)25A · 45m (230V)25A · 50m (230V)25A · 60m (230V)25A · 70m (230V)10A · 25m (230V)16A · 25m (230V)20A · 25m (230V)32A · 25m (230V)40A · 25m (230V)50A · 25m (230V)63A · 25m (230V)80A · 25m (230V)100A · 25m (230V)125A · 25m (230V)160A · 25m (230V)200A · 25m (230V)