Kabeltværsnit for 80 Ampere ved 25 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 80 A over 25 m ved 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 3.42V (1.49%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 4.03V (1.75%)
Voltage at Load226.6 VLine Loss: 273.9 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A57.07 V (24.81%)172.9 V94.13 V (40.93%)4565.3 WDrop High
2.5 mm²24 A18 A34.24 V (14.89%)195.8 V56.48 V (24.56%)2739.2 WDrop High
4 mm²32 A25 A21.4 V (9.3%)208.6 V35.3 V (15.35%)1712.0 WDrop High
6 mm²41 A32 A14.27 V (6.2%)215.7 V23.53 V (10.23%)1141.3 WDrop High
10 mm²57 A44 A8.56 V (3.72%)221.4 V14.12 V (6.14%)684.8 WDrop High
16 mm²76 A59 A5.35 V (2.33%)224.7 V8.82 V (3.84%)428.0 WDrop High
25 mm²101 A78 A3.42 V (1.49%)226.6 V5.65 V (2.46%)273.9 W✓ OK (≤3%)
35 mm²125 A97 A2.45 V (1.06%)227.6 V4.03 V (1.75%)195.7 W✓ OK (≤3%)
50 mm²151 A118 A1.71 V (0.74%)228.3 V2.82 V (1.23%)137.0 W✓ OK (≤3%)
70 mm²192 A150 A1.22 V (0.53%)228.8 V2.02 V (0.88%)97.8 W✓ OK (≤3%)
95 mm²232 A181 A0.9 V (0.39%)229.1 V1.49 V (0.65%)72.1 W✓ OK (≤3%)
120 mm²269 A210 A0.71 V (0.31%)229.3 V1.18 V (0.51%)57.1 W✓ OK (≤3%)
150 mm²309 A241 A0.57 V (0.25%)229.4 V0.94 V (0.41%)45.7 W✓ OK (≤3%)
185 mm²353 A275 A0.46 V (0.2%)229.5 V0.76 V (0.33%)37.0 W✓ OK (≤3%)
240 mm²415 A324 A0.36 V (0.16%)229.6 V0.59 V (0.26%)28.5 W✓ OK (≤3%)
300 mm²477 A372 A0.29 V (0.12%)229.7 V0.47 V (0.2%)22.8 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.09%)229.8 V0.35 V (0.15%)17.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 80 Ampere ved 25 Meter (230V)

Hvilket kabeltværsnit kræves til 80A ved 25 meter (230V)?

Til 80 Ampere over 25 meter ved 230V anbefales 25 mm² kobberkabel (spændingsfald 3.42V / 1.49%).

Hvor mange kW svarer 80A ved 230V til?

Det svarer til 18.4 kW med en anbefalet sikring på 80A.