Kabeltværsnit for 25 Ampere ved 250 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 25 A over 250 m ved 400V.
Copper Cable (≤3% Drop)25 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 10.92V (2.73%)
Voltage at Load390.7 VLine Loss: 401.2 W
Max Power & Breaker17.32 kW25A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 250m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 154.44 V (38.61%) | 245.6 V | 254.76 V (63.69%) | 6687.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 92.66 V (23.17%) | 307.3 V | 152.85 V (38.21%) | 4012.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 57.92 V (14.48%) | 342.1 V | 95.53 V (23.88%) | 2507.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 38.61 V (9.65%) | 361.4 V | 63.69 V (15.92%) | 1671.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 23.17 V (5.79%) | 376.8 V | 38.21 V (9.55%) | 1003.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 14.48 V (3.62%) | 385.5 V | 23.88 V (5.97%) | 627.0 W | ~ ≤5% |
| 25 mm² | 101 A | 78 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 401.2 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 6.62 V (1.65%) | 393.4 V | 10.92 V (2.73%) | 286.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 4.63 V (1.16%) | 395.4 V | 7.64 V (1.91%) | 200.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 3.31 V (0.83%) | 396.7 V | 5.46 V (1.36%) | 143.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.44 V (0.61%) | 397.6 V | 4.02 V (1.01%) | 105.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.93 V (0.48%) | 398.1 V | 3.18 V (0.8%) | 83.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.54 V (0.39%) | 398.5 V | 2.55 V (0.64%) | 66.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.25 V (0.31%) | 398.7 V | 2.07 V (0.52%) | 54.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.97 V (0.24%) | 399.0 V | 1.59 V (0.4%) | 41.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.77 V (0.19%) | 399.2 V | 1.27 V (0.32%) | 33.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.58 V (0.14%) | 399.4 V | 0.96 V (0.24%) | 25.1 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 25 Ampere ved 250 Meter (400V)
Hvilket kabeltværsnit kræves til 25A ved 250 meter (400V)?
Til 25 Ampere over 250 meter ved 400V anbefales 25 mm² kobberkabel (spændingsfald 9.27V / 2.32%).
Hvor mange kW svarer 25A ved 400V til?
Det svarer til 17.32 kW med en anbefalet sikring på 25A.
Related Lengths & Currents (400V)
25A · 5m (400V)25A · 10m (400V)25A · 15m (400V)25A · 20m (400V)25A · 25m (400V)25A · 30m (400V)25A · 35m (400V)25A · 40m (400V)25A · 45m (400V)25A · 50m (400V)25A · 60m (400V)25A · 70m (400V)10A · 250m (400V)16A · 250m (400V)20A · 250m (400V)32A · 250m (400V)40A · 250m (400V)50A · 250m (400V)63A · 250m (400V)80A · 250m (400V)100A · 250m (400V)125A · 250m (400V)160A · 250m (400V)200A · 250m (400V)