Kabeltværsnit for 25 Ampere ved 25 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 25 A over 25 m ved 400V.
Copper Cable (≤3% Drop)4 mm²Drop: 5.79V (1.45%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 9.55V (2.39%)
Voltage at Load394.2 VLine Loss: 250.8 W
Max Power & Breaker17.32 kW25A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 15.44 V (3.86%) | 384.6 V | 25.48 V (6.37%) | 668.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 401.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 5.79 V (1.45%) | 394.2 V | 9.55 V (2.39%) | 250.8 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 3.86 V (0.97%) | 396.1 V | 6.37 V (1.59%) | 167.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.32 V (0.58%) | 397.7 V | 3.82 V (0.96%) | 100.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.45 V (0.36%) | 398.6 V | 2.39 V (0.6%) | 62.7 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.93 V (0.23%) | 399.1 V | 1.53 V (0.38%) | 40.1 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.66 V (0.17%) | 399.3 V | 1.09 V (0.27%) | 28.7 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.46 V (0.12%) | 399.5 V | 0.76 V (0.19%) | 20.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.33 V (0.08%) | 399.7 V | 0.55 V (0.14%) | 14.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.24 V (0.06%) | 399.8 V | 0.4 V (0.1%) | 10.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.19 V (0.05%) | 399.8 V | 0.32 V (0.08%) | 8.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.15 V (0.04%) | 399.8 V | 0.25 V (0.06%) | 6.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.13 V (0.03%) | 399.9 V | 0.21 V (0.05%) | 5.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.1 V (0.02%) | 399.9 V | 0.16 V (0.04%) | 4.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.08 V (0.02%) | 399.9 V | 0.13 V (0.03%) | 3.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.01%) | 399.9 V | 0.1 V (0.02%) | 2.5 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 25 Ampere ved 25 Meter (400V)
Hvilket kabeltværsnit kræves til 25A ved 25 meter (400V)?
Til 25 Ampere over 25 meter ved 400V anbefales 4 mm² kobberkabel (spændingsfald 5.79V / 1.45%).
Hvor mange kW svarer 25A ved 400V til?
Det svarer til 17.32 kW med en anbefalet sikring på 25A.
Related Lengths & Currents (400V)
25A · 5m (400V)25A · 10m (400V)25A · 15m (400V)25A · 20m (400V)25A · 30m (400V)25A · 35m (400V)25A · 40m (400V)25A · 45m (400V)25A · 50m (400V)25A · 60m (400V)25A · 70m (400V)10A · 25m (400V)16A · 25m (400V)20A · 25m (400V)32A · 25m (400V)40A · 25m (400V)50A · 25m (400V)63A · 25m (400V)80A · 25m (400V)100A · 25m (400V)125A · 25m (400V)160A · 25m (400V)200A · 25m (400V)