Kabeltværsnit for 275 Ampere ved 30 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 275 A over 30 m ved 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 2.04V (0.51%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 2.73V (0.68%)
Voltage at Load398.0 VLine Loss: 971.0 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A203.86 V (50.97%)196.1 V336.28 V (84.07%)97102.5 WDrop High
2.5 mm²24 A18 A122.32 V (30.58%)277.7 V201.77 V (50.44%)58261.5 WDrop High
4 mm²32 A25 A76.45 V (19.11%)323.6 V126.1 V (31.53%)36413.4 WDrop High
6 mm²41 A32 A50.97 V (12.74%)349.0 V84.07 V (21.02%)24275.6 WDrop High
10 mm²57 A44 A30.58 V (7.64%)369.4 V50.44 V (12.61%)14565.4 WDrop High
16 mm²76 A59 A19.11 V (4.78%)380.9 V31.53 V (7.88%)9103.4 WDrop High
25 mm²101 A78 A12.23 V (3.06%)387.8 V20.18 V (5.04%)5826.2 WDrop High
35 mm²125 A97 A8.74 V (2.18%)391.3 V14.41 V (3.6%)4161.5 WDrop High
50 mm²151 A118 A6.12 V (1.53%)393.9 V10.09 V (2.52%)2913.1 WDrop High
70 mm²192 A150 A4.37 V (1.09%)395.6 V7.21 V (1.8%)2080.8 WDrop High
95 mm²232 A181 A3.22 V (0.8%)396.8 V5.31 V (1.33%)1533.2 WDrop High
120 mm²269 A210 A2.55 V (0.64%)397.5 V4.2 V (1.05%)1213.8 WDrop High
150 mm²309 A241 A2.04 V (0.51%)398.0 V3.36 V (0.84%)971.0 W✓ OK (≤3%)
185 mm²353 A275 A1.65 V (0.41%)398.3 V2.73 V (0.68%)787.3 W✓ OK (≤3%)
240 mm²415 A324 A1.27 V (0.32%)398.7 V2.1 V (0.53%)606.9 W✓ OK (≤3%)
300 mm²477 A372 A1.02 V (0.25%)399.0 V1.68 V (0.42%)485.5 W✓ OK (≤3%)
400 mm²570 A445 A0.76 V (0.19%)399.2 V1.26 V (0.32%)364.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 275 Ampere ved 30 Meter (400V)

Hvilket kabeltværsnit kræves til 275A ved 30 meter (400V)?

Til 275 Ampere over 30 meter ved 400V anbefales 150 mm² kobberkabel (spændingsfald 2.04V / 0.51%).

Hvor mange kW svarer 275A ved 400V til?

Det svarer til 190.53 kW med en anbefalet sikring på 300A.