⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 30 Ampere ved 10 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 30 A over 10 m ved 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 2.78V (0.69%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 3.06V (0.76%)
Voltage at Load397.2 VLine Loss: 144.4 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.41 V (1.85%)392.6 V12.23 V (3.06%)385.2 WDrop High
2.5 mm²24 A18 A4.45 V (1.11%)395.6 V7.34 V (1.83%)231.1 WDrop High
4 mm²32 A25 A2.78 V (0.69%)397.2 V4.59 V (1.15%)144.4 W✓ OK (≤3%)
6 mm²41 A32 A1.85 V (0.46%)398.1 V3.06 V (0.76%)96.3 W✓ OK (≤3%)
10 mm²57 A44 A1.11 V (0.28%)398.9 V1.83 V (0.46%)57.8 W✓ OK (≤3%)
16 mm²76 A59 A0.69 V (0.17%)399.3 V1.15 V (0.29%)36.1 W✓ OK (≤3%)
25 mm²101 A78 A0.44 V (0.11%)399.6 V0.73 V (0.18%)23.1 W✓ OK (≤3%)
35 mm²125 A97 A0.32 V (0.08%)399.7 V0.52 V (0.13%)16.5 W✓ OK (≤3%)
50 mm²151 A118 A0.22 V (0.06%)399.8 V0.37 V (0.09%)11.6 W✓ OK (≤3%)
70 mm²192 A150 A0.16 V (0.04%)399.8 V0.26 V (0.07%)8.3 W✓ OK (≤3%)
95 mm²232 A181 A0.12 V (0.03%)399.9 V0.19 V (0.05%)6.1 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.02%)399.9 V0.15 V (0.04%)4.8 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.02%)399.9 V0.12 V (0.03%)3.9 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.02%)399.9 V0.1 V (0.02%)3.1 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.01%)400.0 V0.08 V (0.02%)2.4 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.9 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 30 Ampere ved 10 Meter (400V)

Hvilket kabeltværsnit kræves til 30A ved 10 meter (400V)?

Til 30 Ampere over 10 meter ved 400V anbefales 4 mm² kobberkabel (spændingsfald 2.78V / 0.69%).

Hvor mange kW svarer 30A ved 400V til?

Det svarer til 20.78 kW med en anbefalet sikring på 30A.