Kabeltværsnit for 300 Ampere ved 10 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 300 A over 10 m ved 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 0.74V (0.19%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.76V (0.19%)
Voltage at Load399.3 VLine Loss: 385.2 W
Max Power & Breaker207.85 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.13 V (18.53%)325.9 V122.28 V (30.57%)38520.0 WDrop High
2.5 mm²24 A18 A44.48 V (11.12%)355.5 V73.37 V (18.34%)23112.0 WDrop High
4 mm²32 A25 A27.8 V (6.95%)372.2 V45.86 V (11.46%)14445.0 WDrop High
6 mm²41 A32 A18.53 V (4.63%)381.5 V30.57 V (7.64%)9630.0 WDrop High
10 mm²57 A44 A11.12 V (2.78%)388.9 V18.34 V (4.59%)5778.0 WDrop High
16 mm²76 A59 A6.95 V (1.74%)393.1 V11.46 V (2.87%)3611.2 WDrop High
25 mm²101 A78 A4.45 V (1.11%)395.6 V7.34 V (1.83%)2311.2 WDrop High
35 mm²125 A97 A3.18 V (0.79%)396.8 V5.24 V (1.31%)1650.9 WDrop High
50 mm²151 A118 A2.22 V (0.56%)397.8 V3.67 V (0.92%)1155.6 WDrop High
70 mm²192 A150 A1.59 V (0.4%)398.4 V2.62 V (0.66%)825.4 WDrop High
95 mm²232 A181 A1.17 V (0.29%)398.8 V1.93 V (0.48%)608.2 WDrop High
120 mm²269 A210 A0.93 V (0.23%)399.1 V1.53 V (0.38%)481.5 WDrop High
150 mm²309 A241 A0.74 V (0.19%)399.3 V1.22 V (0.31%)385.2 W✓ OK (≤3%)
185 mm²353 A275 A0.6 V (0.15%)399.4 V0.99 V (0.25%)312.3 W✓ OK (≤3%)
240 mm²415 A324 A0.46 V (0.12%)399.5 V0.76 V (0.19%)240.8 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.09%)399.6 V0.61 V (0.15%)192.6 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.07%)399.7 V0.46 V (0.11%)144.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 300 Ampere ved 10 Meter (400V)

Hvilket kabeltværsnit kræves til 300A ved 10 meter (400V)?

Til 300 Ampere over 10 meter ved 400V anbefales 150 mm² kobberkabel (spændingsfald 0.74V / 0.19%).

Hvor mange kW svarer 300A ved 400V til?

Det svarer til 207.85 kW med en anbefalet sikring på 300A.