Kabeltværsnit for 32 Ampere ved 15 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 32 A over 15 m ved 400V.
Copper Cable (≤3% Drop)4 mm²Drop: 4.45V (1.11%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.89V (1.22%)
Voltage at Load395.6 VLine Loss: 246.5 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 11.86 V (2.97%) | 388.1 V | 19.57 V (4.89%) | 657.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 7.12 V (1.78%) | 392.9 V | 11.74 V (2.93%) | 394.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 4.45 V (1.11%) | 395.6 V | 7.34 V (1.83%) | 246.5 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.97 V (0.74%) | 397.0 V | 4.89 V (1.22%) | 164.4 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.78 V (0.44%) | 398.2 V | 2.93 V (0.73%) | 98.6 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.11 V (0.28%) | 398.9 V | 1.83 V (0.46%) | 61.6 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.71 V (0.18%) | 399.3 V | 1.17 V (0.29%) | 39.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.51 V (0.13%) | 399.5 V | 0.84 V (0.21%) | 28.2 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.36 V (0.09%) | 399.6 V | 0.59 V (0.15%) | 19.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.25 V (0.06%) | 399.7 V | 0.42 V (0.1%) | 14.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.19 V (0.05%) | 399.8 V | 0.31 V (0.08%) | 10.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.15 V (0.04%) | 399.9 V | 0.24 V (0.06%) | 8.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 6.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.1 V (0.02%) | 399.9 V | 0.16 V (0.04%) | 5.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.07 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 4.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.06 V (0.01%) | 399.9 V | 0.1 V (0.02%) | 3.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.04 V (0.01%) | 400.0 V | 0.07 V (0.02%) | 2.5 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 32 Ampere ved 15 Meter (400V)
Hvilket kabeltværsnit kræves til 32A ved 15 meter (400V)?
Til 32 Ampere over 15 meter ved 400V anbefales 4 mm² kobberkabel (spændingsfald 4.45V / 1.11%).
Hvor mange kW svarer 32A ved 400V til?
Det svarer til 22.17 kW med en anbefalet sikring på 32A.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 20m (400V)32A · 25m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 15m (400V)16A · 15m (400V)20A · 15m (400V)25A · 15m (400V)40A · 15m (400V)50A · 15m (400V)63A · 15m (400V)80A · 15m (400V)100A · 15m (400V)125A · 15m (400V)160A · 15m (400V)200A · 15m (400V)