Kabeltværsnit for 32 Ampere ved 15 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 32 A over 15 m ved 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 4.45V (1.11%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.89V (1.22%)
Voltage at Load395.6 VLine Loss: 246.5 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.86 V (2.97%)388.1 V19.57 V (4.89%)657.4 WDrop High
2.5 mm²24 A18 A7.12 V (1.78%)392.9 V11.74 V (2.93%)394.4 WDrop High
4 mm²32 A25 A4.45 V (1.11%)395.6 V7.34 V (1.83%)246.5 W✓ OK (≤3%)
6 mm²41 A32 A2.97 V (0.74%)397.0 V4.89 V (1.22%)164.4 W✓ OK (≤3%)
10 mm²57 A44 A1.78 V (0.44%)398.2 V2.93 V (0.73%)98.6 W✓ OK (≤3%)
16 mm²76 A59 A1.11 V (0.28%)398.9 V1.83 V (0.46%)61.6 W✓ OK (≤3%)
25 mm²101 A78 A0.71 V (0.18%)399.3 V1.17 V (0.29%)39.4 W✓ OK (≤3%)
35 mm²125 A97 A0.51 V (0.13%)399.5 V0.84 V (0.21%)28.2 W✓ OK (≤3%)
50 mm²151 A118 A0.36 V (0.09%)399.6 V0.59 V (0.15%)19.7 W✓ OK (≤3%)
70 mm²192 A150 A0.25 V (0.06%)399.7 V0.42 V (0.1%)14.1 W✓ OK (≤3%)
95 mm²232 A181 A0.19 V (0.05%)399.8 V0.31 V (0.08%)10.4 W✓ OK (≤3%)
120 mm²269 A210 A0.15 V (0.04%)399.9 V0.24 V (0.06%)8.2 W✓ OK (≤3%)
150 mm²309 A241 A0.12 V (0.03%)399.9 V0.2 V (0.05%)6.6 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.02%)399.9 V0.16 V (0.04%)5.3 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.02%)399.9 V0.12 V (0.03%)4.1 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)399.9 V0.1 V (0.02%)3.3 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)400.0 V0.07 V (0.02%)2.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 32 Ampere ved 15 Meter (400V)

Hvilket kabeltværsnit kræves til 32A ved 15 meter (400V)?

Til 32 Ampere over 15 meter ved 400V anbefales 4 mm² kobberkabel (spændingsfald 4.45V / 1.11%).

Hvor mange kW svarer 32A ved 400V til?

Det svarer til 22.17 kW med en anbefalet sikring på 32A.