Kabeltværsnit for 32 Ampere ved 50 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 32 A over 50 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 9.78V (2.45%)
Voltage at Load390.1 VLine Loss: 547.8 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A39.54 V (9.88%)360.5 V65.22 V (16.3%)2191.4 WDrop High
2.5 mm²24 A18 A23.72 V (5.93%)376.3 V39.13 V (9.78%)1314.8 WDrop High
4 mm²32 A25 A14.83 V (3.71%)385.2 V24.46 V (6.11%)821.8 W~ ≤5%
6 mm²41 A32 A9.88 V (2.47%)390.1 V16.3 V (4.08%)547.8 W✓ OK (≤3%)
10 mm²57 A44 A5.93 V (1.48%)394.1 V9.78 V (2.45%)328.7 W✓ OK (≤3%)
16 mm²76 A59 A3.71 V (0.93%)396.3 V6.11 V (1.53%)205.4 W✓ OK (≤3%)
25 mm²101 A78 A2.37 V (0.59%)397.6 V3.91 V (0.98%)131.5 W✓ OK (≤3%)
35 mm²125 A97 A1.69 V (0.42%)398.3 V2.8 V (0.7%)93.9 W✓ OK (≤3%)
50 mm²151 A118 A1.19 V (0.3%)398.8 V1.96 V (0.49%)65.7 W✓ OK (≤3%)
70 mm²192 A150 A0.85 V (0.21%)399.2 V1.4 V (0.35%)47.0 W✓ OK (≤3%)
95 mm²232 A181 A0.62 V (0.16%)399.4 V1.03 V (0.26%)34.6 W✓ OK (≤3%)
120 mm²269 A210 A0.49 V (0.12%)399.5 V0.82 V (0.2%)27.4 W✓ OK (≤3%)
150 mm²309 A241 A0.4 V (0.1%)399.6 V0.65 V (0.16%)21.9 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (0.08%)399.7 V0.53 V (0.13%)17.8 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (0.06%)399.8 V0.41 V (0.1%)13.7 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.05%)399.8 V0.33 V (0.08%)11.0 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.04%)399.9 V0.24 V (0.06%)8.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 32 Ampere ved 50 Meter (400V)

Hvilket kabeltværsnit kræves til 32A ved 50 meter (400V)?

Til 32 Ampere over 50 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 9.88V / 2.47%).

Hvor mange kW svarer 32A ved 400V til?

Det svarer til 22.17 kW med en anbefalet sikring på 32A.